| Plan Review Notes For Permit 07040449 |
| Permit Number |
07040449 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-20 08:17:38 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 2) PLANS PAGE 3 OF 3 SHOW A SPLIT A/C SYSTEM BEING | | | INSTALLED AND ALSO NOTED IN THE LOUNGE AREA "WINDOW | | | UNIT A/C TO BE INSTALLED BY OWNER", IF THIS IS CORRECT | | | PLEASE HAVE COOLING LOAD CALCULATIONS AND ENERGY | | | CALCULATIONS SHOW TWO A/C SYSTEMS AND GIVE INFORMATION | | | OF WINDOW UNIT ON A/C EQUIPMENT LISTING. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|