| Date |
Text |
| 2007-04-18 14:04:06 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE EQUIPMENT GROUNDING CONDUCTOR MUST COMPLY WITH |
| | 250.66. INDICATE THE SIZE ON THE PLAN. AN EQUIPMENT |
| | GROUNDING CONDUCTOR MUST BE INSTALLED FROM THE FIRST |
| | MEANS OF DISCONNECT TO THE PANEL PER 250.118, SIZED PER |
| | 250.122. |
| | |
| | 2} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 3} THERE IS AN EQUIPMENT GROUND REQUIRED TO BE RAN WITH |
| | THE FEEDER FROM THE DISCONNECT TO THE PANEL, SEE |
| | 250.122. |
| | |
| | 4} SHOW THE LOCATION OF THE AHU AND A/C DISCONNECTS PER |
| | 440.14,RECEPTACLE PER 210.63, |
| | |
| | 5} THE AHU IS LISTED AS FUTURE ON THE PANEL SCHEDULE, |
| | THERE IS ONE SHOWN ON THE PLAN, ALSO LISTED IN THE |
| | MECHANICAL NOTES AND THERE IS A A/C COMPRESSOR ON THE |
| | SCHEDULE. CORRELATE EQUIPMENT THAT IS TO BE PART OF |
| | THIS PERMIT. |
| | |
| | 6} THERE ARE TWO REFRIGERATORS LISTED ON THE SCHEDULE, |
| | ONLY ONE ON THE PLAN. ALSO DON'T RECOGNIZE EQUIPMENT |
| | CALLED "AIR CONDENSER" OR "PROTECTION" LISTED ON THE |
| | SCHEDULE. SEE 408.4. NEC PLEASE SEE NEW VERBAGE FOR |
| | 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE SUFFICIENT |
| | DETAIL TO ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM |
| | ALL OTHERS." |
| | |
| | 7} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI |
| | PROTECTED PER 210.8(A) (1). NO CIRCUIT IS SHOWN ON THE |
| | SCHEDULE |
| | |
| | 8} THE PANEL SCHEDULE LISTS 2 KITCHEN LIGHT CIRCUITS |
| | AND THERE IS ONLY ONE KITCHEN LIGHT. |
| | |
| | 9} THE PANEL SCHEDULE LISTS TWO SMALL APPLIANCE |
| | CIRCUITS 1 AND2. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |