| Plan Review Notes For Permit 07040431 |
| Permit Number |
07040431 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-03 16:09:19 | | | | | | | DENIED | | | | | | 1)SHUTTER APPLICATIONS REQUIRE A KEY PLAN, SHUTTER | | | SCHEDULE AND THE DRAWINGS THAT ARE PART OF THE PRODUCT | | | APPROVALS CLEARLY MARKED WITH THE INFORMATION SPECIFIC | | | TO THE SITE (TYPE OF CONSTRUCTION, MOUNTING METHOD, | | | ANCHOR TYPE, ETC.) PLEASE SEE THE ATTACHED SCHEDULE | | | | | | 2)THE PRODUCT APPROVALS FOR THE STORM PANELS HAVE | | | INCORRECT DRAWINGS, TO DOWNLOAD THE CORRECT DRAWINGS | | | CLICK ON THE LINK FROM THE FLORIDA PRODUCT APPROVAL | | | THAT YOU HAVE CHOSEN. (FL# 5345 REQUIRES DRAWING # | | | 05-517) | | | | | | 3)THE LIVINGROOM WINDOWS ARE 2 UNITS JOINED TOGETHER | | | AND WILL REQUIRE A MULLION, PLEASE SUBMIT 2 COPIES OF | | | PRODUCT APPROVAL FOR MULLIONS | | | | | | 4)TO ALWAYS BE CURRENT WITH NOA'S PLEASE CHECK THE | | | FLORIDA PRODUCT APPROVAL WEB SITE FOR REVISED PRODUCT | | | APPROVAL (NOTE THE PGT SH-4000 WINDOWS ARE AT REVISION | | | #7 (FL239-R7) THE COVER SHEET THAT YOU HAVE SUBMITTED | | | IS REVISION 4 AND HAS AN OUTDATED NOA AS IT'S | | | COMPLIANCE METHOD, ALTHOUGH YOU HAVE SUBMITTED THE NEW | | | REVISED MIAMI-DADE NOA) | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|