2007-04-24 07:36:26DENIED;
 1.PAGE 3.1 DETAIL A-7 (BREAK SINK) DOOR AND KICK PLAT
 NOT TO CODE. SEE FBC-2004 BUILDING CHAPTER 11 HANDICAP
 CODE SECTION 11-4.24.3, KNEE CLEARANCE REQUIRED UNDER
 THE SINK, 27" HIGH 30" WIDE, AND 19" DEEP. PLEASE SHOW
 A FRONT VIEW ON PLANS AND MAKE REFORANCE TO SECTIONS
 11-4.24.4, DEPTH OF SINK, 11-4.24.6 EXPOSED PIPES AND
 11-4.24.7 FAUSE TO BE LEVER OPERATED.
 2. PAGE D.1.1, KEY NOTE 3; ALL DELETED SANITARY AND
 VENT PIPING MUST BE REMOVED SO NO DEAD ENDS ARE IN THE
 SANITARY SYSTEM. FBC - 2004 PLUMBING SECTION 704.5 .
 3.THE SUBMITED DRAWINGS DO NOT SHOW A DRINKING FOUNTAIN
 IN THE COMMON AREA. IF ONE DOES NOT EXIST THEN THE
 WATER COOLER MUST BE A DRINKING FOUNTAIN WITH A DRAIN.
 SEE TABLE 403.1 AND SECTION 410. THE DRINKING FOUNTAIN
 OR COOLER MUST MEET H/C REQUIREMENTS. SUBMIT CUT SHEET
 FOR WATER COOLER.