| Plan Review Notes For Permit 07040420 |
| Permit Number |
07040420 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-17 14:00:12 | | | | | | | NONCOMPLIANT | | | | | | THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK MUST | | | SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 FAC. THE | | | SEAL IS INDISCERNIBLE. | | | | | | THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE | | | EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS | | | PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT | | | TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS | | | CHANGE. | | | | | | A SEPARATE LOW VOLTAGE PERMIT IS REQUIRED FOR THE | | | ACCESS CONTROL SYSTEM, SPECIFICATIONS FOR ALL DEVICES | | | AND EQUIPMENT MUST BE SUBMITTED WITH THE LOW VOLTAGE | | | APPLICATION. TWO COPIES OF THIS SHEET, SIGNRD AND | | | SEALED MUST BE SUBMITTED WITH THAT APPLICATION FOR | | | RECORD RETENTION. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | | | | |
|