Plan Review Notes
Plan Review Notes For Permit 07040420
Permit Number 07040420
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-17 14:00:12 
  
 NONCOMPLIANT
  
 THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK MUST
 SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 FAC. THE
 SEAL IS INDISCERNIBLE.
  
 THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE.
  
 A SEPARATE LOW VOLTAGE PERMIT IS REQUIRED FOR THE
 ACCESS CONTROL SYSTEM, SPECIFICATIONS FOR ALL DEVICES
 AND EQUIPMENT MUST BE SUBMITTED WITH THE LOW VOLTAGE
 APPLICATION. TWO COPIES OF THIS SHEET, SIGNRD AND
 SEALED MUST BE SUBMITTED WITH THAT APPLICATION FOR
 RECORD RETENTION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  