| 2007-05-31 15:59:25 | BUILDING PLAN REVIEW |
| | PERMIT: 07040404 |
| | ADD:901 45TH STREET. |
| | CONT: STATIC ELECTRIC CO. |
| | TEL: (561)684-6100 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 1ST |
| | ACTION: DENIED |
| | |
| | 1) 2004 FL. BLD CODE 1603.1.4 THE |
| | FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 2)GENERATOR SLAB & ANCHOR REQUIREMENT |
| | PLEASE PROVIDE SIZE OF GENERATOR(WXL), |
| | PLUS PROVIDE PLANS WITH THE INFORMATION |
| | DEPICTING HOLD DOWN BRACKETS, TYPE OF |
| | FASTENER, AND THE MINIMUM EDGE DISTANCE |
| | THE DEVICE REQUIRES WITHOUT LOAD |
| | REDUCTION. |
| | SECOND, PROVIDE INFORMATION ON THE |
| | SLAB, THICKNESS, WIDTH AND LENGTH, IF |
| | WIREMESH, FIBER MESH OR IF STEEL REBAR |
| | WILL BEUSED. |
| | THE NEW SLAB AND HOLD DOWN DETAILS: |
| | 104.2.1* ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 3)PROVIDE PLANS ENOUGH TO VERIFY LOCATION |
| | OF GENERATOR VERSES BUILDING OPENINGS |
| | WINDOWS, DOORS OR SOFFIT TYPE VENTS, |
| | ETC. |
| | M501.2 OUTDOOR DISCHARGE. |
| | THE AIR REMOVED BY EVERY MECHANICAL |
| | EXHAUST SYSTEM SHALL BE DISCHARGED |
| | OUTDOORS AT A POINT WHERE IT WILL NOT |
| | CAUSE A NUISANCE AND FROM WHICH IT |
| | CANNOT AGAIN BE READILY DRAWN IN BY A |
| | VENTILATING SYSTEM. AIR SHALL NOT BE |
| | EXHAUSTED INTO AN ATTIC OR CRAWL SPACE |
| | |
| | M401.5 OPENING LOCATION. |
| | OUTDOOR AIR EXHAUST AND INTAKE OPENINGS |
| | SHALL BE LOCATED A MINIMUM OF 10 FEET |
| | (3048 MM) FROM LOT LINES OR BUILDINGS ON |
| | THE SAME LOT. WHERE OPENINGS FRONT ON A |
| | STREET OR PUBLIC WAY, THE DISTANCE SHALL |
| | BE MEASURED TO THE CENTERLINE OF THE |
| | STREET OR PUBLIC WAY. |
| | |
| | 4) 106.1.3 THE BUILDING OFFICIAL |
| | MAY SET STANDARDS THROUGH DEPARTMENTAL |
| | POLICY STANDARDS FOR PLANS AND SPRCIFICA |
| | TIONS. "NO WHITE OUT OR HAND WRITING ON PLANS". |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |
| | |
| | |
| | |
| | |
| | |