2007-04-17 11:08:18 
 NONCOMPLIANT
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 AS PER INSTRUCTION FROM THE BUILDING OFFICIAL, THIS
 DEPARTMENT REQUIRES ALL PLANS MUST CONTAIN THE PRINTED
 NAME AND SIGNATURE OF THE DESIGNER OF RECORD AS THE
 STATUTE INTENDS. PLEASE COMPLY WITH THIS STATUTE ON ALL
 DOCUMENTS DRAWN BY YOU AND SUBMITTED FOR REVIEW.
  
 PLEASE INDICATE CIRCUIT NUMBERS ON THE DEVICES AND FAN
 SO THAT COMPLIANCE WITH 210.11(C)(1) AND 210.52(B) MAY
 BE DETERMINED.
  
 PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE FOR CLARITY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  