| 2007-04-19 10:49:26 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FACFLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | ***ONLY CHECKED ITEMS APPLY*** |
| | |
| | _XX_1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH |
| | THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13. |
| | |
| | _XX_2.THE DESIGN PRESSURE FOR THE WINDOW (SEE |
| | SHEETS 1 AND 2, -110) DOES NOT MEET THE DESIGN PRESSURE |
| | SPECIFIED BY THE ENGINEER (-143.9). |
| | |
| | _XX_3.PROVIDE A COPY OF THE CONDO ASSOCIATION |
| | APPROVAL. |
| | |
| | _XX_4.MARK THE MULLION PRODUCT APPROVAL TO SHOW |
| | WHICH PRODUCT YOU ARE USING.NOTE THAT FOR A 80" WIDE |
| | OPENING (37+37=74), 63 INCHES HIGH, 1X4 IS LIMITED TO |
| | DESIGN PRESSURE OF -128, BUT THE ENGINEER SPECIFIES |
| | -143.9. |
| | |
| | _XX_5..)PRODUCT APPROVALS ARE TO BE APPROVED BY |
| | DESIGNER OF RECORD, FBC*106.3.3. |
| | |
| | ____6.PROVIDE A FLOOR PLAN SHOWING: WINDOW |
| | LOCATIONS, SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE |
| | EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE |
| | FOR BEDROOMS, FBC R310, FBC EB 505.1. |
| | |
| | _XX_7.COMPLETE THE ATTACHED INSTALLATION SCHEDULE |
| | OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| | ANOTHER FORMAT.(SHUTTERS) |
| | |
| | |