| Plan Review Notes For Permit 07040341 |
| Permit Number |
07040341 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-23 08:56:44 | ****************PROVISO**************** | | | A}FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE | | | GEN/RES PERMIT REQUIRED WITH ZONING APPROVAL OF | | | GENERATOR PLACEMENT. | | | NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET | | | CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES | | | SHALL BE CAPPED GAS TIGHT. IF GAS DELIVERY PRESSURE IS | | | 2 PSI OR GREATER MP REGULATORS SHALL BE INSTALLED PRIOR | | | TO FINAL INSPECTION. | | | | | | B} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR | | | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED | | | IMMEDIATELY AHEAD OF EACH MP REGULATOR. | | | | | | IF DRYER ROOM IS A CONFINED SPACE, OPENINGS REQUIRED | | | PER SECTION 304.5 OR SECTION 304.6 SHALL BE INSTALLED. | | | MINIMUM 1,000 CUBIC FEET REQUIRED. |
|