| Date |
Text |
| 2007-04-20 13:42:05 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. THE SUBMITTED DRAWINGS HAVE AN ENGINEER TITLE BLOCK |
| | FROM THOMAS TWOMEY PE#25626, IF IT IS THE INTENT TO USE |
| | THESE DRAWINGS THEY NEED TO BE SIGNED, SEALED, AND |
| | DATED BY SAID DESIGN PROFESSIONAL PER FBC-2004 CHAPTER |
| | 1, SECTION 106.1 AND PER CHAPTER 471, FLORIDA |
| | STATUTES. |
| | |
| | 2. PER FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION |
| | ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE |
| | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| | AS DETERMINED BY THE |
| | BUILDING OFFICIAL. |
| | NOTE: THE SUBMITTED DRAWINGS ARE CONFUSING AND NEED |
| | CLARIFICATION PER THE FOLLOWING. |
| | A} THERE ARE TWO GAS METERS INDICATED ON THE DRAWINGS, |
| | ONLY ONE IS REQUIRED, PLEASE DELETE ONE ON THE |
| | RESUBMITTAL. |
| | |
| | 3. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: NOT ALL CORRESPONDING LENGTHS ARE INDICATED ON |
| | THE DRAWINGS. PLEASE CORRECT AND RESUBMIT. |
| | |
| | 4. PLEASE NOTE THAT THE GAS SYSTEM IS SIZED WRONG PER |
| | THE FBC-2004 FUEL GAS TABLE 402.4(2) AND THE INDICATED |
| | BTU LOAD OF THE APPLIANCES. PLEASE REFERENCE GAS TABLE |
| | 402.4(2) ATTACHED TO THE GAS COMMENTS INDICATING SYSTEM |
| | IS SIZED WRONG. PLEASE CORRECT AND RESUBMIT. |
| | |
| | 5. SUBMIT MANUFACTURER SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | NOTE: PLEASE SUBMIT TWO COPIES OF MANUFACTURER CUT |
| | SHEETS VERIFYING THE BTU LOAD OF THE APPLIANCES AND |
| | SHOWING A LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY (NRTL) |
| | |
| | 6. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | NOTE: THESE ITEMS ARE INCORRECTLY IDENTIFIED ON THE |
| | SUBMITTED ISOMETRIC GAS RISER DIAGRAM AND NEED TO BE |
| | CORRECTLY INDICATED ON THE RESUBMITTAL. |
| | |
| | 7. PER FBC-2004, CHAPTER 1, SECTION |
| | 108.3, BUILDING PERMIT VALUATION: IF IN |
| | THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF THE BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED. FOR |
| | PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, NORMAL SITE WORK (EXCAVATION AND |
| | BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| | AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| | VALUE. VALUATION REFERENCES MAY INCLUDE |
| | THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS ECT.) WITH |
| | REGIONAL ADJUSTMENTS FOR LOCATION AS |
| | PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. |
| | NOTE: DUE TO THE FACT THAT THE SYSTEM IS SIZED WRONG |
| | AND THE COST OF THE APPLIANCES WERE NOT ACCOUNTED FOR |
| | ON THE PERMITS APPLICATION VALUE, THE VALUE MUST BE |
| | INCREASED ON THE RESUBMITTAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |