Plan Review Notes
Plan Review Notes For Permit 07040304
Permit Number 07040304
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-19 13:47:07 
  
  
  
 PROVISO
  
 FLORIDA BUILDING CODE-2004.
  
 PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE.
  
 EMERGENCY ILLUMINATION MUSR COMPLY WITH
 NFPA-101 7.8 (2003), AND CIRCUITED PER
 700.12 NEC.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718