Plan Review Notes
Plan Review Notes For Permit 07040304
Permit Number 07040304
Review Stop P
Sequence Number 1
Notes
Date Text
2007-04-24 09:09:46DENIED;
 1. PAGE A-1 BREAK SINK TO BE REMOVED, NOTE ( CAP OFF AT
 WALL) TO READ, REMOVE VENT AND SANITARY PIPE TO WITHIN
 24" OF BUILDING DRAIN AND MAIN VENT. SEE FBC-2004
 SECTION 704.5.
 2.PAGE T1, DETAIL 1,BREAK SINK HEIGHT TO BE 2'-10"
 OFF FINISH FLOOR. SECTION 11-4.24.2. ALSO SHOW ON
 DETAIL THE FOLLOWING NOTES AND MEASUREMENTS; KNEE
 CLEARANCE SECTION 11-4.24.3,DEPTH OF SINK SECTION
 11-4.24.4,RAP EXPOSED PIPES SECTION 11-4.24.6 AND
 FAUCET HANDLES SECTION 11-4.24.7.
 3. A SANITARY AND WATER RISER DIAGRAM ARE REQUIRED PER
 CITY OF WEST PALM BEACH CHAPTER 1 ADMINISTRATION CODE
 2004 SECTION106.3.5.1.3(3) AND (4).