| Date |
Text |
| 2007-09-04 20:26:54 | 2007-09-04 20:26:54 |
| | |
| | ** DENIED 3RD REVIEW ** |
| | |
| | ** THIS IS THE SECOND REVIEW UNDER PERMIT. |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL |
| | NEED ADDRESSING. |
| | |
| | |
| | 1) NOTE: PLEASE SEE ALL ARCHITECTURAL SHEETS IN BOTH |
| | SETS ARE NOT SEALED AS REQUIRED PER FS 481.221. THIS IS |
| | REQUIRED FOR ALL SHEETS IN BOTH SETS. |
| | |
| | 2) NOTE:PLEASE SEE THE ENERGY CALCULATIONS THAT WERE |
| | SUBMITTED ARE NOT SEALED ON THE SHEET WHICH |
| | SPECIFICALLY CALLS FOR THE CERTIFICATIONS TO BE MADE. ( |
| | IT WAS NOTICED THAT ONE OF THE SHEETS IN THE REAR OF |
| | THE SHEETS WAS SIGNED, AND SEALED) |
| | PLEASE SEE 13-103.1.1.1 AS THIS IS REQUIRED ON EACH OF |
| | THE TWO SETS BEING REQUESTED TO BE SUBMITTED FOR |
| | REVIEW. PLEASE SEE FAC 61G15-23.002 AND FS 471.025 |
| | |
| | 3) NOTE:AS STATED ON THE PREVIOUS REVIEWS, PLEASE |
| | INCLUDE LOCATIONS OF ALL OVER RIDE DEVICES BEING |
| | INSTALLED AND AS REQUIRED PER 13-415.1.ABC.1.1 AND |
| | .1.2. |
| | PLEASE SEE THE SAME SECTIONS OF CODE AS THE OVER RIDES |
| | SHALL BE LOCATED SO THAT THE OCCUPANT CAN VISUALLY SEE |
| | THE LIGHTING WHICH IS BEING CONTROLLED. THERE IS ONE |
| | EXCEPTION WHICH THE USE OF PILOT LIGHTS MAY BE USED, |
| | HOWEVER NEITHER THE LOCATION OF THE DEVICES FOR OVER |
| | RIDE FOR CONTROL OF LIGHTING IS SHOWN ON PLANS AS |
| | REQUIRED PER CODE OR PILOT LIGHTS ARE DETAILED ON |
| | PLANS. |
| | PLEASE ALSO SEE THAT THE TYPE OF OVER RIDE DEVICE(S) |
| | SHALL STATE THEIR MAXIMUM TIMES BASED ON THE TYPE OF |
| | DEVICE CHOSEN. |
| | THE PREVIOUS REVIEW NOTE WITH RESPECT TO MORE |
| | INFORMATION NEEDED FOR LIGHTING CONTROLS, OVER RIDES |
| | AND SEPARATE SPACES WAS RESPONDED BY THE MENTION OF A |
| | BATTERY BACK UP FIXTURE IN THE BATHROOMS?? |
| | PLEASE PROVIDE INFORMATION ON THE OVER RIDES, |
| | LOCATIONS, TIMES ON OVER RIDES, SEPARATE SPACE DEVICES |
| | ETC. THE ONLY TIME WHICH COULD BE LOCATED FOR NOTE #101 |
| | WAS MOTION WITH 15MINS. |
| | PLEASE SEE THE MOTION SENSOR DEVICE WHICH IS BEING |
| | ASSUMED AS MS ON PLANS WILL NOT BE ACCEPTED BY THIS |
| | OFFICE IN MULTI-USE RESTROOMS WITH PARTITION TYPE |
| | WALLS. THESE WOULD NEED TO BE COMBO TYPE DEVICES SUCH |
| | AS ULTRASONIC ETC. |
| | PLEASE SEE NOTE #4 FROM BOTH PREVIOUS REVIEWS. THIS |
| | OFFICE CAN NOT EXPLAIN IN TYPE WRITTEN NOTES ANY |
| | FURTHER. PLEASE CALL TO GO OVER AND FOR QUESTIONS |
| | REGARDING THIS. |
| | |
| | 4) NOTE:PLEASE SEE AS STATED ON PREVIOUS REVIEW(S). |
| | PLEASE COORDINATE ALL FIXTURES ON PLANS, FIXTURE LEGEND |
| | AND THE ENERGY CALCULATIONS BEING SUBMITTED. PLEASE SEE |
| | THESE STILL DO NOT CORRELATE. |
| | PLEASE SEE THE LIGHTING FIXTURE LEGEND: FOR EXAMPLE: |
| | PLEASE SEE THE WATTAGE OF EACH TYPE OF FIXTURE DOES NOT |
| | APPEAR ON THE ENERGY CALCULATIONS AS SHOWN. (60WATT |
| | FIXTURES ETC) |
| | PLEASE SEE THE TOTAL NUMBER OF FIXTURES FOR EXAMPLE OF |
| | THE 124WATT FIXTURES SHOWN AS A TOTAL OF185 ON |
| | FIXTURE LEGEND INDICATES A TOTAL OF 215 ON |
| | CALCULATIONS. THIS IS THE SAME FOR 62 WATT FIXTURES. |
| | PLEASE NOT ONLY COORDINATE THE FIXTURE LEGEND WITH THE |
| | CALCULATIONS BUT ALSO COORDINATE WITH THE FIXTURES ON |
| | PLANS. |
| | PLEASE SEE 13-415.2, 13-415.1.B (AS METHOD B IS BEING |
| | SUBMITTED) |
| | |
| | 5) NOTE: PLEASE KNOW FEES ARE OWED BEFORE ISSUANCE OF |
| | PERMIT BASED ON THE INCREASED VALUE AS STATED ON LETTER |
| | FROM PHILLIPS PARTNERSHIP. |
| | PLEASE KNOW THAT WHEN PLANS ARE SUBMITTED FOR THE |
| | FOLLOWING REVIEW, THE RE-SUB FEE OF 10% WILL BE DUE AT |
| | TIME OF RE-SUBMISSION OF PLANS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** AS STATED ON PREVIOUS REVIEW: |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |