Plan Review Notes
Plan Review Notes For Permit 07040301
Permit Number 07040301
Review Stop E
Sequence Number 3
Notes
Date Text
2007-09-04 20:26:542007-09-04 20:26:54
  
 ** DENIED 3RD REVIEW **
  
 ** THIS IS THE SECOND REVIEW UNDER PERMIT.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED ADDRESSING.
  
  
 1) NOTE: PLEASE SEE ALL ARCHITECTURAL SHEETS IN BOTH
 SETS ARE NOT SEALED AS REQUIRED PER FS 481.221. THIS IS
 REQUIRED FOR ALL SHEETS IN BOTH SETS.
  
 2) NOTE:PLEASE SEE THE ENERGY CALCULATIONS THAT WERE
 SUBMITTED ARE NOT SEALED ON THE SHEET WHICH
 SPECIFICALLY CALLS FOR THE CERTIFICATIONS TO BE MADE. (
 IT WAS NOTICED THAT ONE OF THE SHEETS IN THE REAR OF
 THE SHEETS WAS SIGNED, AND SEALED)
 PLEASE SEE 13-103.1.1.1 AS THIS IS REQUIRED ON EACH OF
 THE TWO SETS BEING REQUESTED TO BE SUBMITTED FOR
 REVIEW. PLEASE SEE FAC 61G15-23.002 AND FS 471.025
  
 3) NOTE:AS STATED ON THE PREVIOUS REVIEWS, PLEASE
 INCLUDE LOCATIONS OF ALL OVER RIDE DEVICES BEING
 INSTALLED AND AS REQUIRED PER 13-415.1.ABC.1.1 AND
 .1.2.
 PLEASE SEE THE SAME SECTIONS OF CODE AS THE OVER RIDES
 SHALL BE LOCATED SO THAT THE OCCUPANT CAN VISUALLY SEE
 THE LIGHTING WHICH IS BEING CONTROLLED. THERE IS ONE
 EXCEPTION WHICH THE USE OF PILOT LIGHTS MAY BE USED,
 HOWEVER NEITHER THE LOCATION OF THE DEVICES FOR OVER
 RIDE FOR CONTROL OF LIGHTING IS SHOWN ON PLANS AS
 REQUIRED PER CODE OR PILOT LIGHTS ARE DETAILED ON
 PLANS.
 PLEASE ALSO SEE THAT THE TYPE OF OVER RIDE DEVICE(S)
 SHALL STATE THEIR MAXIMUM TIMES BASED ON THE TYPE OF
 DEVICE CHOSEN.
 THE PREVIOUS REVIEW NOTE WITH RESPECT TO MORE
 INFORMATION NEEDED FOR LIGHTING CONTROLS, OVER RIDES
 AND SEPARATE SPACES WAS RESPONDED BY THE MENTION OF A
 BATTERY BACK UP FIXTURE IN THE BATHROOMS??
 PLEASE PROVIDE INFORMATION ON THE OVER RIDES,
 LOCATIONS, TIMES ON OVER RIDES, SEPARATE SPACE DEVICES
 ETC. THE ONLY TIME WHICH COULD BE LOCATED FOR NOTE #101
 WAS MOTION WITH 15MINS.
 PLEASE SEE THE MOTION SENSOR DEVICE WHICH IS BEING
 ASSUMED AS MS ON PLANS WILL NOT BE ACCEPTED BY THIS
 OFFICE IN MULTI-USE RESTROOMS WITH PARTITION TYPE
 WALLS. THESE WOULD NEED TO BE COMBO TYPE DEVICES SUCH
 AS ULTRASONIC ETC.
 PLEASE SEE NOTE #4 FROM BOTH PREVIOUS REVIEWS. THIS
 OFFICE CAN NOT EXPLAIN IN TYPE WRITTEN NOTES ANY
 FURTHER. PLEASE CALL TO GO OVER AND FOR QUESTIONS
 REGARDING THIS.
  
 4) NOTE:PLEASE SEE AS STATED ON PREVIOUS REVIEW(S).
 PLEASE COORDINATE ALL FIXTURES ON PLANS, FIXTURE LEGEND
 AND THE ENERGY CALCULATIONS BEING SUBMITTED. PLEASE SEE
 THESE STILL DO NOT CORRELATE.
 PLEASE SEE THE LIGHTING FIXTURE LEGEND: FOR EXAMPLE:
 PLEASE SEE THE WATTAGE OF EACH TYPE OF FIXTURE DOES NOT
 APPEAR ON THE ENERGY CALCULATIONS AS SHOWN. (60WATT
 FIXTURES ETC)
 PLEASE SEE THE TOTAL NUMBER OF FIXTURES FOR EXAMPLE OF
 THE 124WATT FIXTURES SHOWN AS A TOTAL OF185 ON
 FIXTURE LEGEND INDICATES A TOTAL OF 215 ON
 CALCULATIONS. THIS IS THE SAME FOR 62 WATT FIXTURES.
 PLEASE NOT ONLY COORDINATE THE FIXTURE LEGEND WITH THE
 CALCULATIONS BUT ALSO COORDINATE WITH THE FIXTURES ON
 PLANS.
 PLEASE SEE 13-415.2, 13-415.1.B (AS METHOD B IS BEING
 SUBMITTED)
  
 5) NOTE: PLEASE KNOW FEES ARE OWED BEFORE ISSUANCE OF
 PERMIT BASED ON THE INCREASED VALUE AS STATED ON LETTER
 FROM PHILLIPS PARTNERSHIP.
 PLEASE KNOW THAT WHEN PLANS ARE SUBMITTED FOR THE
 FOLLOWING REVIEW, THE RE-SUB FEE OF 10% WILL BE DUE AT
 TIME OF RE-SUBMISSION OF PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** AS STATED ON PREVIOUS REVIEW:
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved