| Date |
Text |
| 2007-07-02 15:22:14 | 2007-07-02 15:22:14 |
| | |
| | *** UNSAT *** |
| | |
| | |
| | *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET |
| | SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE |
| | REVIEWED AT THIS TIME. |
| | |
| | |
| | ** PLEASE SEE THERE ARE STILL COMMENTS FROM PREVIOUS |
| | REVIEW WHICH ARE IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE RESPONSE LETTER FROM THE DESIGNER |
| | IS QUOTING THE ELECTRICAL REVIEW COMMENTS HOWEVER THE |
| | COMMENTS AS BEING QUOTED ARE NOT THAT IN ITS ENTIRETY |
| | OF THIS REVIEWERS COMMENT. PLEASE SEE COMMENT #7 FOR |
| | EXAMPLE. PLEASE BE SURE IF QUOTING COMMENTS FROM TRADES |
| | THEY ARE AS ACCURATE AS POSSIBLE. THIS HELPS THE REVIEW |
| | PROCESS. PLEASE SEE NOTE # 7 FROM PREVIOUS REVIEW AS |
| | THE RESPONSE ONLY SEEMS TO MENTION ONE PART OF THE |
| | PREVIOUS NOTES. |
| | FBC 106.3 |
| | |
| | 2) NOTE:PLEASE SEE THERE ARE SEVERAL SHEETS IN THE |
| | ARCHITECTURAL PLANS WHICH ARE SHEETS NOT CORRECT OR |
| | CHANGED FROM PREVIOUS REVIEW. PLEASE SEE THESE SHEETS |
| | WHICH WERE NOT CHANGED DO NOT CONTAIN THE REQUIRED |
| | INFORMATION. |
| | PLEASE ALSO SEE THE MEP PLANS WHICH DO NOT CONTAIN THE |
| | INFORMATION AS NEEDED EVEN THOUGHT THE TITLE BLOCKS ARE |
| | LISTED? |
| | ** THIS IS REQUIRED. |
| | PLEASE SEE THE SHEETS FROM THE ARCHITECT WERE NOT DATED |
| | AS REQUIRED UNDER FS 481.221 NEW AND OLD SHEETS. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE MISSING INFORMATION REQUIRED ON TITLE BLOCKS |
| | FOR ARCHITECTURAL FIRM AS REQUIRED UNDER FAC |
| | 61G1-16.004 AND FS 481.219. |
| | PLEASE SEE THE MISSING PRINTED NAME, PRINTED LICENSE |
| | NUMBER OF THE DESIGNER OF RECORD ALONG WITH THE MISSING |
| | CERTIFICATE OF AUTHORIZATION NUMBER. |
| | **THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY ANY OTHER TRADES. |
| | |
| | 3) NOTE:PLEASE SEE ONLY ONE SET OF ENERGY |
| | CALCULATIONS WERE SUBMITTED. PLEASE SEE THIS SET WAS |
| | NOT SEALED AS REQUIRED ONLY SIGNED AND DATED BY THE |
| | DESIGNER OF RECORD. PLEASE ALSO SEE THE OWNER AGENT IS |
| | STILL NOT SIGNED. |
| | PLEASE SEE 13-103.1.1.1 AS THIS IS REQUIRED ON EACH OF |
| | THE TWO SETS BEING REQUESTED TO BE SUBMITTED FOR |
| | REVIEW. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT SEPARATE ENERGY CALCULATIONS AS THE |
| | SEPARATE SHEETS. THE INFORMATION MAY STILL BE ON PLANS; |
| | HOWEVER THE SEPARATE SHEETS ARE NEEDED. |
| | PLEASE BE SURE TO SIGN, DATE AND SEAL. |
| | FBC 13-103.1.1.1 |
| | |
| | 4) NOTE: THE PREVIOUS REVIEW NOTE WITH RESPECT TO MORE |
| | INFORMATION NEEDED FOR LIGHTING CONTROLS, OVER RIDES |
| | AND SEPARATE SPACES WAS RESPONDED BY THE MENTION OF A |
| | BATTERY BACK UP FIXTURE IN THE BATHROOMS?? |
| | PLEASE PROVIDE INFORMATION ON THE OVER RIDES, |
| | LOCATIONS, TIMES ON OVER RIDES, SEPARATE SPACE DEVICES |
| | ETC. THE ONLY TIME WHICH COULD BE LOCATED FOR NOTE #101 |
| | WAS MOTION WITH 15MINS. |
| | PLEASE SEE THE MOTION SENSOR DEVICE WHICH IS BEING |
| | ASSUMED AS MS ON PLANS WILL NOT BE ACCEPTED BY THIS |
| | OFFICE IN MULTI-USE RESTROOMS WITH PARTITION TYPE |
| | WALLS. THESE WOULD NEED TO BE COMBO TYPE DEVICES SUCH |
| | AS ULTRASONIC ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE CLARIFY NEW CONTROL METHODS FOR NEW LIGHTING |
| | BEING INSTALLED. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE SOME NOTES TO OCCUPANCY SENSOR TYPE DEVICES |
| | ARE NOTED, HOWEVER TIMES OF MAXIMUM PERMITTED TIMES ARE |
| | NOT SHOWN. |
| | PLEASE ALSO SEE THAT THE MS TYPE DEVICE NOTED FOR |
| | BATHROOMS WILL NOT PROVIDE NEEDED COVERAGE FOR THE LIFE |
| | SAFETY ASPECT OF LIGHTING CONTROL. PLEASE ADJUST THE |
| | TYPE OF DEVICE. |
| | LS 101 7.8,7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE |
| | LIGHTING SWITCHES SHALL BE PERMITTED WITHIN THE MEANS |
| | OF EGRESS, PROVIDED THAT THE SWITCH CONTROLLERS ARE |
| | EQUIPPED FOR FAIL-SAFE OPERATION, THE ILLUMINATION |
| | TIMERS ARE SET FOR A MINIMUM 15-MINUTE DURATION, AND |
| | THE MOTION SENSOR IS ACTIVATED BY ANY OCCUPANT MOVEMENT |
| | IN THE AREA SERVED BY THE LIGHTING UNITS. |
| | PLEASE ALSO SEE CHAPTER 10 OF THE FBC. 1006. |
| | |
| | 5) NOTE: PLEASE SEE THE VALUE AS APPLIED SEEMS LOW. |
| | PLEASE KNOW THE VALUE SHALL INCLUDE ALL LIGHTING |
| | FIXTURES EQUIPMENT ETC EVEN IF ANY OF THESE ITEMS ARE |
| | OWNER SUPPLIED. |
| | |
| | **PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW WHEN APPLYING FOR PERMIT, THE VALUE FOR |
| | THE COMPLETE SCOPE OF WORK SHALL INCLUDE ALL LABOR AND |
| | MATERIALS EVEN IF EQUIPMENT, FIXTURES ETC ARE OWNER |
| | SUPPLIED. |
| | PLEASE KNOW THAT A VALUE MAY BE USED USING THE ADOPTED |
| | GUIDES UNDER THE FBC 108.3 |
| | |
| | 6) NOTE:PLEASE SEE THE NUMBER OF FIXTURES ARE NOW |
| | SHOWN ON FIXTURE LEGEND AS REQUESTED HOWEVER PLEASE SEE |
| | THERE ARE SOME MINOR DIFFERENCES IN THE ENERGY |
| | CALCULATIONS AND THE FIXTURE LEGEND FIXTURES. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE THE NUMBER OF FIXTURES IN THE FIXTURE |
| | LEGEND FOR EACH AND COORDINATE WITH THE ENERGY |
| | CALCULATIONS WHICH ARE TO BE REVISED. |
| | FBC CHAPTER 13, 13-415.2, 13-415.1.AB.1.1 ETC PLEASE |
| | SEE TABLES FOR METHOD B AND INDICATE ACCORDINGLY. ** |
| | PLEASE VERIFY THE WATTAGE ETC SHOWN FOR THE *JELLY JAR* |
| | FIXTURE. |
| | |
| | ** PLEASE KNOW THERE MAY BE NEW COMMENTS ONCE |
| | ADDITIONAL INFORMATION IS SUBMITTED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-07-02 14:22:02 | 2007-07-02 14:22:02 |
| | PLANS REMOVED FROM INCOMING AND WILL BE RETURNED TO |
| | INCOMING WAITING FOR COMM BOARD ONCE ELECTRICLA REVIEW |
| | IS DONE. |