Plan Review Notes
Plan Review Notes For Permit 07040301
Permit Number 07040301
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-06-01 15:30:22*****DENIED*****
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE REMOVAL AND (OR) THE REPLACEMENT OF BUILDING
 MATERIALS & SUPPLIES SHALL NOT HINDER OR INTERFERE WITH
 EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF (INCLUDING FIRE LANES).
  
 4.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE EXTERIOR
 ELEVATION WHICH FRONTS OKEECHOBEE BOULEVARD.AS PER
 WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH.
  
 5.SHOW THE LOCATION OF THE 2A10:BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFIES THE 75' TRAVEL
 DISTANCE.
  
 6.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN THE EXITS, EXIT ACCESS CORRIDORS, AND
 OTHER SPACES AS CLASS A, CLASS B. OR CLASS C.
  
 7.WILL THE SCOPE OF WORK HAVE CAUSE FOR THE FIRE
 SPRINKLERS TO BE ALTERED OR MODIFIED?IF SO, SEPARATE
 PLANS SND PERMIT WILL BE REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722