| Plan Review Notes For Permit 07040301 |
| Permit Number |
07040301 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-01 15:30:22 | *****DENIED***** | | | | | | | | | 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.THE REMOVAL AND (OR) THE REPLACEMENT OF BUILDING | | | MATERIALS & SUPPLIES SHALL NOT HINDER OR INTERFERE WITH | | | EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR | | | VICINITY THEREOF (INCLUDING FIRE LANES). | | | | | | 4.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE EXTERIOR | | | ELEVATION WHICH FRONTS OKEECHOBEE BOULEVARD.AS PER | | | WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS | | | THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH. | | | | | | 5.SHOW THE LOCATION OF THE 2A10:BC RATED FIRE | | | EXTINGUISHER(S) WHICH SATISFIES THE 75' TRAVEL | | | DISTANCE. | | | | | | 6.SPECIFY THE INTERIOR WALL AND CEILING FINISH | | | MATERIALS IN THE EXITS, EXIT ACCESS CORRIDORS, AND | | | OTHER SPACES AS CLASS A, CLASS B. OR CLASS C. | | | | | | 7.WILL THE SCOPE OF WORK HAVE CAUSE FOR THE FIRE | | | SPRINKLERS TO BE ALTERED OR MODIFIED?IF SO, SEPARATE | | | PLANS SND PERMIT WILL BE REQUIRED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS | | | ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|