| Date |
Text |
| 2007-04-21 15:33:27 | ** UNSAT ** |
| | |
| | ** PLEASE SEE ANY REFERENCES TO CHAPTER 1 OF THE FBC |
| | ARE THE ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY |
| | OF WEST PALM BEACH. |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. THIS |
| | WOULD INCLUDE REQUIRED CODES ON TRADE SHEETS. PLEASE |
| | KNOW THERE ARE CHANGES IN THE FBC WHICH MAY AFFECT |
| | DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON |
| | TITLE BLOCKS FOR ARCHITECTURAL FIRM AS REQUIRED UNDER |
| | FAC 61G1-16.004 AND FS 481.219. |
| | PLEASE SEE THE MISSING PRINTED NAME, PRINTED LICENSE |
| | NUMBER OF THE DESIGNER OF RECORD ALONG WITH THE MISSING |
| | CERTIFICATE OF AUTHORIZATION NUMBER. |
| | **THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY ANY OTHER TRADES. |
| | |
| | 3) NOTE: PLEASE ALSO SEE THE MISSING INFORMATION |
| | REQUIRED FOR THE ENGINEERING FIRM AS REQUIRED UNDER FAC |
| | 61G15-23.002 AND FS 471.023. |
| | PLEASE SEE THE MISSING PRINTED NAME AND MISSING |
| | CERTIFICATE OF AUTHORIZATION NUMBER. |
| | THIS IS REQUIRED ON ALL SHEETS WHICH CONTAIN THE TITLE |
| | BLOCK FOR ENGINEERING FIRM AND DESIGNERS OF RECORD. |
| | |
| | 4) NOTE: PLEASE SEE THE M AND P SHEETS WHICH ARE SEALED |
| | WITH A SEAL WHICH IS NO LONGER VALID IN THE STATE OF |
| | FLORIDA. PLEASE SEE FAC 61G15-23.001 WHICH IN FEB 04 |
| | CHANGED TO REQUIRE THE WORDING OF *LICENSE* IN SAID |
| | SEAL INSTEAD OF THE WORDING OF *CERTIFICATE*. |
| | AN EXTENSION WAS ISSUED BY THE FLORIDA BOARD OF |
| | PROFESSIONAL ENGINEERS TO THE DATE OF DECEMBER 31ST, |
| | 2005 HOWEVER ALL PLANS AFTER THAT DATE MUST CONTAIN THE |
| | NEW SEAL. *PLEASE OBTAIN*. |
| | |
| | 5) NOTE: PLEASE SEE THE SEAL AS NOTED IN NOTE #4 ABOVE |
| | SHALL BE OF MINIMUM SIZE AS REQUIRED UNDER FAC |
| | 61G15-23.001. (2INCHES) |
| | THE SEAL AT THIS TIME IS NOT OF THE REQUIRED MINIMUM |
| | SIZE. THIS IS NOT A NEW RULING. |
| | REQUIRED WHETHER OR NOT THIS IS NOTED BY OTHER TRADES. |
| | |
| | 6) NOTE: PLEASE SEE THE VERSION OF THE FLORIDA ENERGY |
| | CODE IS NOT CORRECT. PLEASE SEE THE NEW ADOPTED FBC |
| | 2004 W/ 2006 REVISIONS IN CHAPTER 13. |
| | |
| | PLEASE SUBMIT SEPARATE ENERGY CALCULATIONS AS THE |
| | SEPARATE SHEETS. THE INFORMATION MAY STILL BE ON PLANS, |
| | HOWEVER THE SEPARATE SHEETS ARE NEEDED. |
| | PLEASE BE SURE TO SIGN, DATE AND SEAL. |
| | FBC 13-103.1.1.1 |
| | |
| | 7) NOTE: PLEASE CLARIFY NEW CONTROL METHODS FOR NEW |
| | LIGHTING BEING INSTALLED. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE SOME NOTES TO OCCUPANCY SENSOR TYPE DEVICES |
| | ARE NOTED, HOWEVER TIMES OF MAXIMUM PERMITTED TIMES ARE |
| | NOT SHOWN. |
| | PLEASE ALSO SEE THAT THE MS TYPE DEVICE NOTED FOR |
| | BATHROOMS WILL NOT PROVIDE NEEDED COVERAGE FOR THE LIFE |
| | SAFETY ASPECT OF LIGHTING CONTROL. PLEASE ADJUST THE |
| | TYPE OF DEVICE. |
| | LS 101 7.8,7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE |
| | LIGHTING SWITCHES SHALL BE PERMITTED WITHIN THE MEANS |
| | OF EGRESS, PROVIDED THAT THE SWITCH CONTROLLERS ARE |
| | EQUIPPED FOR FAIL-SAFE OPERATION, THE ILLUMINATION |
| | TIMERS ARE SET FOR A MINIMUM 15-MINUTE DURATION, AND |
| | THE MOTION SENSOR IS ACTIVATED BY ANY OCCUPANT MOVEMENT |
| | IN THE AREA SERVED BY THE LIGHTING UNITS. |
| | PLEASE ALSO SEE CHAPTER 10 OF THE FBC. 1006. |
| | |
| | 8) NOTE: PLEASE KNOW WHEN APPLYING FOR PERMIT, THE |
| | VALUE FOR THE COMPLETE SCOPE OF WORK SHALL INCLUDE ALL |
| | LABOR AND MATERIALS EVEN IF EQUIPMENT, FIXTURES ETC ARE |
| | OWNER SUPPLIED. |
| | PLEASE KNOW THAT A VALUE MAY BE USED USING THE ADOPTED |
| | GUIDES UNDER THE FBC 108.3 |
| | |
| | 9) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3(4) FOR ANY |
| | FA DEVICES FOR ADA COMPLIANCE WHICH MAY BE REQUIRED TO |
| | BE CHANGED OR INSTALLED. |
| | PLEASE SEE REVIEWS FROM OTHER TRADES,( FIRE MARSHAL) IF |
| | ANY WORK TO THESE EXISTING SYSTEMS ARE TAKING PLACE, |
| | THIS BASE INFORMATION SHALL BE INCLUDE ON THESE BASE |
| | PLANS EVEN WHEN THESE SYSTEMS ARE UNDER SEPARATE |
| | PERMIT. |
| | FBC 106.3.5.1.2 |
| | |
| | 10) NOTE: PLEASE INDICATE THE NUMBER OF FIXTURES IN THE |
| | FIXTURE LEGEND FOR EACH AND COORDINATE WITH THE ENERGY |
| | CALCULATIONS WHICH ARE TO BE REVISED. |
| | FBC CHAPTER 13, 13-415.2, 13-415.1.AB.1.1 ETC PLEASE |
| | SEE TABLES FOR METHOD B AND INDICATE ACCORDINGLY. |
| | ** PLEASE VERIFY THE WATTAGE ETC SHOWN FOR THE *JELLY |
| | JAR* FIXTURE. |
| | |
| | 11) NOTE: PLEASE KNOW THAT ALL LV WORK FOR SOUND |
| | SYSTEMS, ETC WILL BE REQUIRED TO BE UNDER A SEPARATE |
| | PERMIT, HOVER MAY BE SHOWN ON THESE PLANS. |
| | ONCE PLANS ARE STAMPED THE LV CONTRACTOR/ELECTRICAL |
| | CONTRACTOR WOULD ONLY NEED TO FILL OUT PERMIT |
| | APPLICATION, APPROPRIATE VALUE AND REFERENCE MAIN |
| | PLANS. PERMIT WILL BE ISSUED THE SAME TIME AS A |
| | *TURN-AROUND*. |
| | ANY QUESTIONS ON THIS PLEASE CALL. |
| | |
| | 12) NOTE: PLEASE KNOW THAT PLANS HAVE ONLY BEEN |
| | SUBMITTED FOR *PLAN REVIEW ONLY* AND HAVE NOT BEEN |
| | SUBMITTED FOR PERMIT. |
| | ONCE PLANS ARE CODE COMPLIANT AND ALL INFORMATION IS |
| | SUBMITTED, PLANS CAN NOT BE STAMPED UNTIL PERMIT IS |
| | APPLIED FOR SO THAT VERIFICATION OF LICENSURE, PERMIT |
| | VALUE ETC CAN BE VERIFIED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |