| 2007-06-13 08:07:18 | BUILDING PLAN REVIEW |
| | PERMIT: 07040301 |
| | ADD: 2497 OKEECHOBEE BLVD |
| | CONT: "PLAN REVIEW" |
| | TEL: (650)952-4400 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3)PHILLIPS PARTNERSHIP, IS MISSING THEIR CERTIFICATE |
| | OF AUTHORIZATION,481.219 F.S.CERTIFICATE OF |
| | AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING |
| | THE NAME OF AN ARCHITECT |
| | PRACTICING UNDER A FICTITIOUS NAME, ACORPORATION, OR |
| | A PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES, SHALL |
| | INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER.ADD |
| | THE NUMBER TO EACH SHEET. |
| | |
| | 4)THE MECHANICAL AND PLUMBING SHEETS HAVE THE DESIGN |
| | PROFESSIONAL USING AN INVALID SEAL.RULE |
| | 61G15-23.001(1) F.A.C.THE FLORIDA BOARD OF |
| | PROFESSIONAL |
| | ENGINEERS HAS CLEANED UP THE APPEARANCE OF THE SEAL BY |
| | ELIMINATING OBSOLETE CONTENT AND CHANGING THE WORD |
| | "CERTIFICATE" TO "LICENSE". A GRACE PERIOD RAN THROUGH |
| | DEC. 31,2005.PURSUANT TO SECTION 471.025 F. S. , THE |
| | BOARD HEREBY ESTABLISHES AS INDICATED BELOW THE FORMS |
| | OF EMBOSSING IMPRESSION SEALS WHICH ARE ACCEPTABLE TO |
| | THE BOARD. |
| | SAID SEAL SHALL BE A MINIMUM OF 1 7/8" IN DIAMETER. ALL |
| | ENGINEERS MUST BE UTILIZING SEALS AS ILLUSTRATED IN |
| | THIS RUKE NO LATER THAN JANUARY 1, 2006. |
| | |
| | 5) BEWARE OF EXTERIOR WORK TO BE COMPLETED DURING |
| | HURRICANE SEASON. 109.3.10.1 HURICANE PROTECTION. IT |
| | SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION |
| | RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE |
| | OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 |
| | HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSONS WHO FAILS TO COMPLY TO |
| | REMOVE OR SECURE THE CONSTRUCTION MATERIALS EQUIPMENT |
| | AND DEBRIS WITHIN 24 HRS AFTER A HURRICANE WATCH HAS |
| | BEENISSUED SHALL BE SUBJECT TO A FINE NOT TO EXCEED |
| | $500.00. |
| | IN ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO |
| | VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE |
| | PURSUANT TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 6) IT APPEARS THE FRONT DOORS ARE TO BE REPLACED AND |
| | EFIS WORK WILL ALSO BE REPLACED.FL BLD CODE |
| | 1609.1.4: COMPONENTS & CLADDING, PROVIDE 2 COPIES(3 IF |
| | THRESHOLD OR RESIDENT INSPECTOR) OF PRODUCT TESTING |
| | REPORTS ,MISSING REPORTS ARE AS FOLLOWS: |
| | A) EXTERIOR GLAZED DOORS |
| | B) EFIS SYSTEMS |
| | |
| | 7)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 8)) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 9) FOR WORK ON THE EXTERIOR OF THE BUILDING WIND |
| | INFORMATION WILL BE NEEDED FOR THE DESIGN: |
| | 2004 FL. BLD CODE 1603.1.4 THE |
| | FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 10) SHEET A-0, CODE INFORMATION BUILDING TYPE "2C" |
| | PLEASE SEE 2004 FBC TABLE 503 AND SECTION 602 FOR |
| | BUILDING CLASSIFICATION. |
| | |
| | 11) SHEET A-0, CODE INFORMATION OCCUPANCY LEFT BLANK? |
| | SEE 302.1 |
| | |
| | 12) SHEET A-0 INDICATES CODE INFORMATION AS DESIGNED TO |
| | THE 2004 FBC, PLEASE UPDATE INCLUDING THE2006 |
| | AMENDMENTS. |
| | |
| | 13) SHEET A-0 THIS IS AN INTERIOR RENOVATIION OF AN |
| | EXISTING SPACE, PLEASE SEE 2004/ 2006 UPDATES TO THE |
| | FLORIDA EXISTING BUILDING CODE., TO WHICH LEVEL WILL |
| | THIS ALTERATION BE? |
| | |
| | 14) SHEET A-0 INDICATES ENERGY CALCS WERE ATTACHED, |
| | WHERE? |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |