2007-06-13 08:07:18BUILDING PLAN REVIEW
 PERMIT: 07040301
 ADD: 2497 OKEECHOBEE BLVD
 CONT: "PLAN REVIEW"
 TEL: (650)952-4400
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)PHILLIPS PARTNERSHIP, IS MISSING THEIR CERTIFICATE
 OF AUTHORIZATION,481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, ACORPORATION, OR
 A PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER.ADD
 THE NUMBER TO EACH SHEET.
  
 4)THE MECHANICAL AND PLUMBING SHEETS HAVE THE DESIGN
 PROFESSIONAL USING AN INVALID SEAL.RULE
 61G15-23.001(1) F.A.C.THE FLORIDA BOARD OF
 PROFESSIONAL
 ENGINEERS HAS CLEANED UP THE APPEARANCE OF THE SEAL BY
 ELIMINATING OBSOLETE CONTENT AND CHANGING THE WORD
 "CERTIFICATE" TO "LICENSE". A GRACE PERIOD RAN THROUGH
 DEC. 31,2005.PURSUANT TO SECTION 471.025 F. S. , THE
 BOARD HEREBY ESTABLISHES AS INDICATED BELOW THE FORMS
 OF EMBOSSING IMPRESSION SEALS WHICH ARE ACCEPTABLE TO
 THE BOARD.
 SAID SEAL SHALL BE A MINIMUM OF 1 7/8" IN DIAMETER. ALL
 ENGINEERS MUST BE UTILIZING SEALS AS ILLUSTRATED IN
 THIS RUKE NO LATER THAN JANUARY 1, 2006.
  
 5) BEWARE OF EXTERIOR WORK TO BE COMPLETED DURING
 HURRICANE SEASON. 109.3.10.1 HURICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION MATERIALS EQUIPMENT
 AND DEBRIS WITHIN 24 HRS AFTER A HURRICANE WATCH HAS
 BEENISSUED SHALL BE SUBJECT TO A FINE NOT TO EXCEED
 $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 6) IT APPEARS THE FRONT DOORS ARE TO BE REPLACED AND
 EFIS WORK WILL ALSO BE REPLACED.FL BLD CODE
 1609.1.4: COMPONENTS & CLADDING, PROVIDE 2 COPIES(3 IF
 THRESHOLD OR RESIDENT INSPECTOR) OF PRODUCT TESTING
 REPORTS ,MISSING REPORTS ARE AS FOLLOWS:
 A) EXTERIOR GLAZED DOORS
 B) EFIS SYSTEMS
  
 7)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8)) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9) FOR WORK ON THE EXTERIOR OF THE BUILDING WIND
 INFORMATION WILL BE NEEDED FOR THE DESIGN:
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 10) SHEET A-0, CODE INFORMATION BUILDING TYPE "2C"
 PLEASE SEE 2004 FBC TABLE 503 AND SECTION 602 FOR
 BUILDING CLASSIFICATION.
  
 11) SHEET A-0, CODE INFORMATION OCCUPANCY LEFT BLANK?
 SEE 302.1
  
 12) SHEET A-0 INDICATES CODE INFORMATION AS DESIGNED TO
 THE 2004 FBC, PLEASE UPDATE INCLUDING THE2006
 AMENDMENTS.
  
 13) SHEET A-0 THIS IS AN INTERIOR RENOVATIION OF AN
 EXISTING SPACE, PLEASE SEE 2004/ 2006 UPDATES TO THE
 FLORIDA EXISTING BUILDING CODE., TO WHICH LEVEL WILL
 THIS ALTERATION BE?
  
 14) SHEET A-0 INDICATES ENERGY CALCS WERE ATTACHED,
 WHERE?
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]