| Plan Review Notes For Permit 07040295 |
| Permit Number |
07040295 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-12 07:57:14 | DENIED; | | | 1. PAGE 1 (FLOOR PLAN NOTE) 14. TOILET ROOM FINISH, | | | PLEASE SPECIFY MATERIAL TO BE USED ON THE FLOOR AND | | | WALLS. SECTION 1210.2 REQUIRES A SMOOTH HARD SURFACE | | | WITHIN 2' OF THE TOILET AND TO A HEIGHT OF 4' FROOM THE | | | FLOOR. PAINT IS NOT A HARD SURFACE IT CAN CHIP OR | | | SCRATCHED. | | | 2. SINK-1 IS NOT SHOWN ON THE SANITARY RISER DIAGRAM. | | | 3. WATER RISER, IF THE "T" AT THE TOP OF THE DROPS | | | INDICATE WATER HAMMER ARRESTORS PLEASE LOWER THEM TO | | | THE BOTTOM OF THE DROPS. SEE SECTION 604.9. WATER | | | HAMMER ARRESTORS ARE NOT REQUIRED BUT IF INSTALLED THEY | | | MUST BE INSTALLED CLOSE TO THE SOURCE OF HAMMER PER | | | MANUFATURE SPECIFICATIONS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|