| Plan Review Notes For Permit 07040295 |
| Permit Number |
07040295 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-11 10:42:27 | *** DENIED *** | | | 1) SEE PAGE 2 A/C PLAN, V.D. FOR NEW 6" O.S.A. DUCT | | | NEED TO BE INTHE SPACE THE A/C UNIT IT IS SERVING IS | | | IN. | | | | | | 2) THE 6" O.S.A. DUCT WILL REQUIRE A FIRE DAMPER WERE | | | IT PENETRATES THE RATED TENANT SEPARATION PARTITION OR | | | SHOW HOW IT MEETS THE EXCEPTIONS OF 2004 FBC/M | | | 607.5.3. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|