2007-04-13 12:48:29***DENIED***
  
 1) PLEASE SEE MECHANICAL COMMENT REGARDING A FIRE
 DAMPER. NEW INSTALLATIONS SHALL BE TESTED FOR CLOSURE
 IN ACCORDANCE WITH UL 555 PRIOR TO FINAL INSPECTION.
  
 2) IN ACCORDANCE WITH LOCAL REQUIREMENTS, DUCT SMOKE
 DETECTORS TO INITIATE A GENERAL FIRE ALARM IF
 APPLICABLE.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
  