Plan Review Notes
Plan Review Notes For Permit 07040295
Permit Number 07040295
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-25 14:59:56 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 SHEET #2 OF THE ENERGY GAUGE ONLY LISTS 1 FLUORESCENT,
 AND NOTE THAT ALTHOUGH A MANUAL CONTROL IS LISTED, IT
 MUST AUTOMATICALLY TURN LIGHTS OFF WITHIN 30 MINUTES OF
 ALL OCCUPANTS LEAVING THE SPACE PER 13-415.1ABC.1.2(A).
 DESIGNATE WHICH MANUFACTURER AND MODELS ARE BEING
 SPECIFIED FOR THIS PROJECT BY THE ENGINEER.
  
 CORRELATE THE FIXTURE SCHEDULE WITH THE ENERGY CALCS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  