| Plan Review Notes For Permit 07040295 |
| Permit Number |
07040295 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-25 14:59:56 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW | | | | | | SHEET #2 OF THE ENERGY GAUGE ONLY LISTS 1 FLUORESCENT, | | | AND NOTE THAT ALTHOUGH A MANUAL CONTROL IS LISTED, IT | | | MUST AUTOMATICALLY TURN LIGHTS OFF WITHIN 30 MINUTES OF | | | ALL OCCUPANTS LEAVING THE SPACE PER 13-415.1ABC.1.2(A). | | | DESIGNATE WHICH MANUFACTURER AND MODELS ARE BEING | | | SPECIFIED FOR THIS PROJECT BY THE ENGINEER. | | | | | | CORRELATE THE FIXTURE SCHEDULE WITH THE ENERGY CALCS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|