Plan Review Notes
Plan Review Notes For Permit 07040274
Permit Number 07040274
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-06-01 12:49:28*****DENIED*****
  
  
 1.THE COMPLETE ADDRESS OF THE PROJECT LOCATION SHALL
 BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
 PLEASE NOTE THAT THE NUMBER 6329 IS MISSING.
  
 2.PRECAUTIONS SHALL BE TAKEN TO PREVENT THE IGNITION
 OF FLAMMABLE VAPORS FROM THE VARIOUS SOURCES BEFORE,
 DURING, AND AFTER THE PROJECTED SCOPE OF WORK.
  
 3.SMOKING SHALL BE PERMITTED ONLY IN DESIGNATED AND
 PROPERLY IDENTIFIED AREAS.
  
 4.ALL METALLIC EQUIPMENT WHERE AN IGNITABLE MIXTURE
 COULD BE PRESENT SHALL BE BONDED OR GROUNDED.
  
 5.UNSUPERVISED, ISOLATED ABOVEGROUND STORAGE TANKS
 SHALL BE SECURED AND MARKED IN SUCH A MANNER AS TO
 IDENTIFY THE FIRE HAZARDS OF THE TANK AND THE TANK'S
 CONTENT.THE AREA IN WHICH THE TANK IS LOCATED SHALL
 BE PROTECTED FROM TAMPERING OR TREPASSING, WHERE
 NECESSARY.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722