| Date |
Text |
| 2007-04-21 13:30:40 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE STATE ON PLANS ALL UPDATED DATED |
| | ADOPTED CODES AS OF DECEMBER 8TH, 2006 WHICH MUTS |
| | INCLUDE THE FOLLOWING AT A MINIMUM FOR ELECTRICAL. |
| | NFPA-70 2005, 2004 FBC W/ 2006 REVISIONS. |
| | ** SEE OTHER TRADE REVIEWS FOR ANY OTHER CODES. |
| | |
| | 2) NOTE: PLEASE PROVIDE A LAYOUT FOR ALL CLASS AND |
| | DIVISION LOCATIONS PER NEC 514. |
| | PLEASE INDICATE THE DISTANCE FOR EPO DEVICE. PLEASE SEE |
| | THE MINIMUM/MAXIMUM 541.11C |
| | |
| | 3) NOTE: PLEASE INDICATE ANY INCREASE OF LOAD ON THE |
| | PANEL WHICH IS SHOWN AS EXISTING. |
| | 220 |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE PROVIDE FURTHER DETAIL FOR GROUNDING AS |
| | NOTED. PLEASE INDICATE SIZING, ATTACHMENT LOCATIONS. |
| | (NEW AND/OR EXISTING MEETING CURRENT CODE.514.16, 250, |
| | 501.130 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |