| 2007-06-13 12:33:42 | BUILDING PLAN REVIEW |
| | PERMIT: 07040274 |
| | ADD: 6329 N JOG RD |
| | CONT: DELTA PETROLEUM |
| | TEL: (561)722-1632 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 2A) THE REPLACEMENT OF THE ABOVE GROUND DIESEL TANK |
| | DOESN'T PROVIDE ANY MANUFACTURERES INFORMATION, PLEASE |
| | PROVIDE ADDITIONAL INFORMATION. IF THIS SYSTEM PROVIDES |
| | A DOUBLE WALLED TANK, IF SO OF WHAT TYPE OF MATERIAL? |
| | FBC 4115.2.5 |
| | 2B) THE SECOND CONCERN IS IF THE TANK TO BE PROVIDED IS |
| | A DOUBLE WALLED TANK HOW WOULD ONE KNOW IF THERE IS A |
| | LEAK BETWEEN THE TANKS? IS THERE AN LEAKAGE ALARM OR |
| | SIGNAL OF SOME TYPE? FBC 415.7.2.6 |
| | 2C) IN THE FUEL SYSTEM SITE WORK FOR THE REMOVAL OF THE |
| | OLD 5,000 DIESEL TANK THE PLANS INDICATE THE OLD |
| | CONTAINMENT WALL AND PEDESTALS WERE TO BE REMOVED. |
| | SECTION FBC 415.7.2.2 IT INDICATES EITHER A FIRE |
| | BARRIER WALL OR HORIZONTAL ASSEMBLIES OR BOTH AROUND |
| | THE STORAGE TANK SHALL BE PERMITTED. |
| | |
| | 3) SHEET 2OF 2 TANK ANCHOR DETAIL INDICATES(1)1" |
| | REDHEAD TO BE INSTALLED INTO A 3,000 PSI SLAB. THE PLAN |
| | DOES NOT INDICATE HOW MANY ANCHORS WILL NEED TO BE |
| | INSTALLED TO RESIST THE MOMENT OF OVERTURNING?NOR |
| | DOES THE PLAN INDICATE IF THIS IS A NEW SLAB OR A |
| | REUSED SLAB. THERE IS A SLAB DETAIL FOR A FUEL SLAB? |
| | |
| | 4) THIS SAME ANCHORING SYSTEM DOES NOT PROVIDE ALL THE |
| | WIND INFO REQUIRED.2004 FL. BLD CODE 1603.1.4 THE |
| | FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING CATEGORY (FUEL |
| | DISPENSING FACILITY) |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | |
| | 5) 406.5.1 CONSTRUCTION.MOTOR FUEL-DISPENSING |
| | FACILITIES SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE |
| | FLORIDA FIRE PREVENTION CODE AND THIS SECTION. |
| | |
| | 6) PLEASE PROVIDE THE MSDS SHEETS FOR DIESEL. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |