2007-06-13 12:33:42BUILDING PLAN REVIEW
 PERMIT: 07040274
 ADD: 6329 N JOG RD
 CONT: DELTA PETROLEUM
 TEL: (561)722-1632
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2A) THE REPLACEMENT OF THE ABOVE GROUND DIESEL TANK
 DOESN'T PROVIDE ANY MANUFACTURERES INFORMATION, PLEASE
 PROVIDE ADDITIONAL INFORMATION. IF THIS SYSTEM PROVIDES
 A DOUBLE WALLED TANK, IF SO OF WHAT TYPE OF MATERIAL?
 FBC 4115.2.5
 2B) THE SECOND CONCERN IS IF THE TANK TO BE PROVIDED IS
 A DOUBLE WALLED TANK HOW WOULD ONE KNOW IF THERE IS A
 LEAK BETWEEN THE TANKS? IS THERE AN LEAKAGE ALARM OR
 SIGNAL OF SOME TYPE? FBC 415.7.2.6
 2C) IN THE FUEL SYSTEM SITE WORK FOR THE REMOVAL OF THE
 OLD 5,000 DIESEL TANK THE PLANS INDICATE THE OLD
 CONTAINMENT WALL AND PEDESTALS WERE TO BE REMOVED.
 SECTION FBC 415.7.2.2 IT INDICATES EITHER A FIRE
 BARRIER WALL OR HORIZONTAL ASSEMBLIES OR BOTH AROUND
 THE STORAGE TANK SHALL BE PERMITTED.
  
 3) SHEET 2OF 2 TANK ANCHOR DETAIL INDICATES(1)1"
 REDHEAD TO BE INSTALLED INTO A 3,000 PSI SLAB. THE PLAN
 DOES NOT INDICATE HOW MANY ANCHORS WILL NEED TO BE
 INSTALLED TO RESIST THE MOMENT OF OVERTURNING?NOR
 DOES THE PLAN INDICATE IF THIS IS A NEW SLAB OR A
 REUSED SLAB. THERE IS A SLAB DETAIL FOR A FUEL SLAB?
  
 4) THIS SAME ANCHORING SYSTEM DOES NOT PROVIDE ALL THE
 WIND INFO REQUIRED.2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING CATEGORY (FUEL
 DISPENSING FACILITY)
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
  
 5) 406.5.1 CONSTRUCTION.MOTOR FUEL-DISPENSING
 FACILITIES SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE
 FLORIDA FIRE PREVENTION CODE AND THIS SECTION.
  
 6) PLEASE PROVIDE THE MSDS SHEETS FOR DIESEL.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  