| Plan Review Notes For Permit 07040254 |
| Permit Number |
07040254 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-13 16:12:02 | *** DENIED *** | | | 1) FLOOR PLAN DESIGN IS NOT OF GOOD QUALITY, UNABLE TO | | | DEFINE WHAT THE ROOMS ARE, IF THEIR ARE DOORS, WERE THE | | | AIR HANDLER IS LOCATED (IN CLOSET, OUT IN ROOM, OR IN | | | ATTIC), NEED TO STATE ON PLANS IF FIRST OR SECOND | | | FLOOR | | | | | | 2) MECHANICAL PLANS ARE DIFFICULT TO READ. CONSTRUCTION | | | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY. PER 2004 FBC | | | 106.1.1. | | | | | | 3) SHOW LOCATION OF THE TWO CONDENSER UNITS ON THE | | | PLANS. | | | | | | 4) SHOW LOCATION OF DRAIN LINES ON PLANS. | | | | | | 5) SHOW SEER OF A/C SYSTEMS ON PLANS. | | | | | | 6) SHOW HOW RETURN AIR IS GETTING FROM ROOMS TO AIR | | | HANDLER. | | | | | | 7) PLEASE SUBMIT PLANS THAT LOOK SOME-WHAT | | | PROFESSIONAL. SEE 2004 FBC 106.1.1 AND CITY WPB AMEND. | | | 106.1.3 QUALITY OF BUILDING PLANS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|