Plan Review Notes
Plan Review Notes For Permit 07040251
Permit Number 07040251
Review Stop P
Sequence Number 1
Notes
Date Text
2007-04-24 10:08:39****************PROVISO****************
 1) FBC-2004 SEC. 424.2.7.1, OR FBCR-2004 SEC.R4101.7.1
 POOL CIRCULATING PUMPS
 SHALL BE EQUIPPED ON THE INLET SIDE WITH
 AN APPROVED TYPE HAIR AND LINT STRAINER
 WHEN USED WITH A PRESSURE FILTER.
 (DETAIL OR ADD TO NOTES)
 2) FBC-2004 SEC. 424.2.14.4, OR
 FBCR-2004 SEC. R4101.14.4 CONNECTIONS,
 ALL WATER HEATING EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO THE HEATER.
 (ADD TO NOTES)
 3) FBC-2004 SEC. 424.2.14, OR FBCR-2004
 SEC. R4101.15 GAS PIPING SHALL COMPLY
 WITH FBC FUEL GAS.SEPARATE PLANS AND
 PERMIT REQUIRED.