2007-06-21 15:54:07****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)PRESSURES DO NOT MATCH THE ENGINEERING.SEE YOU
 DESIGN PRESSURES ON THE INSTALLATION SCHEDULE AND THE
 ENGINEERING.HOW HAVE YOU ARRIVED AT THESE NUMBER?
 YOU NEED TO USE THE NUMBERS ON THE ENGINEERING.
  
 2.)3" EDGE DISTANCE REQUIRES A DECREASE IN ANCHOR
 SPACING, SEE SHEET5.
  
 3.)SPANS SPECIFIED 11'10 EXCEED ALLOWABLE SPAN OF
 11'.IT IS NOT CLEAR WHY YOU ARE USING A 11'10" SPAN
 FOR AN 8' OPENING.PLEASE REVISE.
  
  