| 2007-04-19 08:23:19 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FACFLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.)DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED |
| | FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED |
| | ORIGINALS FS481. |
| | |
| | 2.)IT APPEARS THAT SOMEONE OTHER THAN THE ARCHITECT |
| | ALTERED THIS PLAN.INCORPORATE CHANGES INTO THE PLAN. |
| | |
| | 3.)BUILDING TYPE IS BASED ON FBC2001.REVISE TO A |
| | BUILDING TYPE IN FBC2004 CHAPTER 5, INCLUDING A OR B. |
| | |
| | 4.)SEE FBC7 AND STATE WHICH TYPE OF FIRE RESISTIVE |
| | WALL THIS IS (FIRE WALL, FIRE PARTITION, FIRE BARRIER, |
| | FBC705, 706, 708). |
| | |
| | 5.)SHOW COMPLETE CODE COMPLIANCE FOR THIS OPENING |
| | BASED ON OPENING PROTECTIVE REQUIREMENTS FOR THIS FIRE |
| | RESISTIVE WALL TYPE, SEE COMMENT 4. |
| | |
| | 6.)THIS WALL IS SHOWN AS A SMOKE BARRIER.SHOW |
| | COMPLIANCE WITH FBC710.5. |
| | |
| | 7.)DECLARE OCCUPANCY, FBC CHAPTER 3. |
| | |
| | 8.)PROVIDE DIMENSIONS ON THE PLAN, AND AN ELEVATION |
| | IF NECESSARY, TO DETERMINE FBC2406.3(6) REQUIREMENTS. |
| | IF THIS IS CONSIDERED A HAZARDOUS LOCATION, SHOW |
| | COMPLIANCE WITH FBC2406 IN THE WINDOW SPECIFICATIONS. |
| | |
| | 9.)DESIGNER OF RECORD TO REVIEW/APPROVE THE PROPOSED |
| | GLAZING PRODUCT. |
| | |
| | |
| | |
| | |
| | |