| 2007-07-06 10:14:05 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)COMMENT FROM FIRST LIST, REVISE EXPOSURE CATEGORY. | | | ON THE INSTALLATION SCHEDULE YOU'VE STATED THAT THIS IS | | | EXPOSURE C BUT RAN WIND LOAD SOFTWARE AS EXPOSURE B. | | | THE PRESSURES SHOULD BE OVER -40PSF.THE ANCHOR | | | SPACING YOU HAVE SPECIFIED IS NOT COMPLIANT FOR | | | EXPOSURE C. | | | |
|