Plan Review Notes
Plan Review Notes For Permit 07040221
Permit Number 07040221
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-12 15:46:37 
  
  
 1} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES PER 108.3 FBC AS
 AMENDED. INCREASE THE VALUE AT THE
 COUNTER AND RESUBMIT.
  
 2} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD.
  
 3} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1)
 AND 210.52 (A) (2).
  
 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY. THE CONTRACTOR OF RECORD MAY BE THE
 DESIGN PROFESSIONAL IF EXEMPTIONS UNDER THOSE STATUTES
 ARE APPLICABLE. THE ENGINEER MUST PROVIDE A TITLE
 BLOCK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718