Plan Review Notes
Plan Review Notes For Permit 07040211
Permit Number 07040211
Review Stop P
Sequence Number 2
Notes
Date Text
2007-07-09 14:02:58DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A **NO** IS IF THE COMMENT WAS NOT FULLY ADDRESSED
 AND/OR FURTHER EXPLANATION OR CHANGES IN PLANS OR
 DOCUMENTS ARE STILL NEEDED. THIS REVIEWER WILL TRY TO
 BETTER EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN **OK** WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A **NO/OK** MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **OK**
  
 2. **OK**
  
 3. **OK**
  
 4. **NO**PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
 NOTE: THE RESUBMITTED DRAWINGS STILL DO NOT HAVE A
 SANITARY ISOMETRIC RISER DIAGRAM REQUIRED FOR PLUMBING
 PLAN REVIEW. AGAIN PLEASE REFERENCE AN EXAMPLE OF THE
 PROPOSED BATHROOM SANITARY ISOMETRIC RISER DIAGRAM
 ATTACHED TO THE DENIED PLUMBING COMMENTS FOR THE
 RESUBMITTAL.
  
 5. **OK**
  
 6. **OK**
  
 7. **NO/OK** FBC-2004 CHAPTER 1,SECTION 106.3.4.2: THE
 PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
 NOTE: NOT ALL RESUBMITTED DRAWINGS HAD THE PRINTED AND
 SIGNED NAMES OF THE PERSON RESPOSIBLE FOR THE DRAWINGS.
 TWO COMPLETE SETS OF SIGNED DRAWINGS ARE REQUIRED.
  
 **THE FOLLOWING ARE NEW COMMENTS.**
 NOTE: THE RESUBMITTED INFORMATION IS INDICATING THAT
 THIS IS A NEW BATHROOM THAT WAS AN OLD STORAGE CLOSET.
 THIS PROJECT SHOULD HAVE BEENSUBMITTED AS A
 RESIDENTIAL RENOVATION WITH PLAN REVIEWS FROM
 ELECTRICAL, MECHANICAL, BUILDING AS WELL AS THIS
 PLUMBING PLAN REVIEW.
  
 8. PER FBC-2004 CHAPTER 1, SECTION 106: CONSTRUCTION
 DOCUMENTS SUBMITTED IN PENCIL ARE UNACCEPTABLE, PLEASE
 RESUBMIT ANY FUTURE DRAWINGS IN INK.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  