| 2007-04-09 11:58:05 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.)TWO ORIGINAL SETS OF ALL PERMIT DOCUMENTS |
| | REQUIRED, FBC*106.1.ONLY ONE SET OF ENGINEERING WAS |
| | SUBMITTED. |
| | |
| | 2.)THE ENGINEER SPECIFIES TIN CAP NAILING AND MAKES |
| | NO REFERENCE TO THE SPECIFIC NOA OR ASSEMBLY.THE |
| | ASSEMBLY SPECIFIES SIMPLEX MEGA CAP NAILS. |
| | |
| | 3.)THE ENGINEERING SPECIFIES SPACING BUT NOT NUMBER |
| | OF ROWS. |
| | |
| | 4.)THE ENGINEER SPECIFIES 3" SPACING.SEE RAS117 8.1 |
| | IN REGARDS TO MINIMUM FASTENER SEPARATION. |
| | |
| | 5.)PROVIDE CALCULATIONS IN ACCORDANCE WITH RAS117; |
| | SEE GENERAL LIMITATION #7 OF THE NOA.ONLY A |
| | SPECIFICATION WAS PROVIDED; CALCULATIONS ARE REQUIRED. |
| | |
| | 5.)SEE ATTACHED POLICY IN REGARDS TO INFORMATION TO |
| | BE INCLUDED IN THE PRODUCT APPROVAL.NOT ENOUGH SHEETS |
| | WERE PROVIDED.IF YOU ARE UNSURE AS TO WHAT TO SUBMIT |
| | (BUT FIRST PLEASE READ THE POLICY AS IT SPECIFICALLY |
| | STATES WHAT IS REQUIRED), SUBMIT A COMPLETE PRODUCT |
| | APPROVAL WITH THE APPROVED ASSEMBLY CLEARLY MARKED AND |
| | I WILL REMOVE THE UNNECESSARY SHEETS. |
| | |
| | 6.)THE ENGINEERING HAS BEEN RETAINED. |