Plan Review Notes For Permit 07040189
Permit Number 07040189
Review Stop B
Sequence Number 5
Notes
Date Text
2007-08-30 18:13:17****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 FROM PREVIOUS LIST:
  
 4.)THE SHUTTER CONNECTION MOUNTING TYPE IS BLANK.
 THIS SHOULD BE A THROUGH L, SEE THE PRODUCT APPROVAL
 ANCHOR SCHEDULES.
  
 THIS SHOULD BE A THROUGH L, SEE THE PRODUCT APPROVAL
 ANCHOR SCHEDULES.SEE PAGE 14.YOU HAVE HIGHLIGHTED
 F, G, AND H.SPECIFY WHICH CONNECTION TYPE GOES WITH
 EACH OPENING, TOP AND BOTTOM.
  
 NEW COMMENT, 6TH REVIEW:
  
 YOU'VE HIGHLIGHTED THREE DIFFERENT CONNECTION TYPES.
 CONNECTION E REQUIRES 7" SPACING.
  
 INSTALLATION SCHEDULE STATES "WALL", BUT NONE OF THE
 WALL CONNECTION TYPES ON SHEET 13 ARE HIGHLIGHTED.
 WALL TYPES WILL BE A THROUGH E.IF YOU ARE USING E,
 WHICH IS HIGHLIGHTED, 7" ANCHOR SPACING REQUIRED.
 YOU'VE SPECIFIED 7.5".CODE COMPLIANCE CANNOT BE
 DETERMINED UNTIL YOU PROVIDE THIS INFORMATION.