Plan Review Notes
Plan Review Notes For Permit 07040189
Permit Number 07040189
Review Stop B
Sequence Number 2
Notes
Date Text
2007-07-16 18:37:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 FROM PREVIOUS LIST:
  
 _XX_4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.ALL INFORMATION IS REQUIRED.
  
  
 _XX_9.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2),
 FBC R301.2.1.4 OR PROVIDE JUSTIFICATION FOR EXPOSURE B
 PRESSURES (AERIALS OR SURVEY WITH DIMENSIONS).NOTE
 THAT THE DEFINITION FOR EXPOSURE C HAS CHANGED
 EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC R301.2.1.4.
  
 2ND REVIEW - YOU'VE SUPPLIED NEW WIND LOAD CALCS BUT
 THE DESIGN PRESSURE ON THE INSTALLATION SCHEDULE IS
 STILL FOR EXPOSURE B.