| Plan Review Notes For Permit 07040180 |
| Permit Number |
07040180 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-19 15:47:49 | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | | FBC2004 | | | FACFLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)ACCORDION SHUTTER SPANS SHOULD CORRELATE TO THE | | | VERTICAL DIMENSION,BUT THE SCHEDULE SHOWS THE SHUTTER | | | SPANS ON THE HORIZONTAL DIMENSION.REVISE EITHER THE | | | SPAN OR THE OPENING (WXH).A 10' SPAN WOULD REQUIRE | | | CLOSER ANCHOR SPACING THAN WHAT YOU HAVE SPECIFIED; SEE | | | PRODUCT APPROVAL. | | | | | | 2.)PROVIDE CALCULATIONS FOR THE DESIGN PRESSURES. | | | SEE FBC TABLE 1609.6.2.1(2).THE PRESSURES YOU HAVE | | | SPECIFIED ARE LOWER THAN 50SF, ZONE 4 140MPH PRESSURES | | | ON THE TABLE. | | | | | | 3.)TWO IDENTICAL SETS OF PERMIT DOCUMENTS ARE TO BE | | | SUBMITTED, FBC*106.1.SEE THE ANCHOR SCHEDULE, TWO | | | DIFFERENT ONES WERE SUBMITTED. | | | | | | | | | | | | | | | |
|