2007-04-19 15:47:49SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)ACCORDION SHUTTER SPANS SHOULD CORRELATE TO THE
 VERTICAL DIMENSION,BUT THE SCHEDULE SHOWS THE SHUTTER
 SPANS ON THE HORIZONTAL DIMENSION.REVISE EITHER THE
 SPAN OR THE OPENING (WXH).A 10' SPAN WOULD REQUIRE
 CLOSER ANCHOR SPACING THAN WHAT YOU HAVE SPECIFIED; SEE
 PRODUCT APPROVAL.
  
 2.)PROVIDE CALCULATIONS FOR THE DESIGN PRESSURES.
 SEE FBC TABLE 1609.6.2.1(2).THE PRESSURES YOU HAVE
 SPECIFIED ARE LOWER THAN 50SF, ZONE 4 140MPH PRESSURES
 ON THE TABLE.
  
 3.)TWO IDENTICAL SETS OF PERMIT DOCUMENTS ARE TO BE
 SUBMITTED, FBC*106.1.SEE THE ANCHOR SCHEDULE, TWO
 DIFFERENT ONES WERE SUBMITTED.
  
  
  
  
  