| Plan Review Notes For Permit 07040115 |
| Permit Number |
07040115 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-06-15 11:20:14 | TRUSS LAYOUT AND DRAWINGS IS DENIED | | | | | | 1) THE TRUSS LAYOUT IS REQUIRED TO BE SIGNED AND SEALED | | | BY THE TRUSS ENGINEER AND REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD FOR THE STRUCTURE. | | | FAC 61G-15-23.002 AND FS471. | | | | | | 2) THE TRUSS DRAWING COVER SHEET IS REQUIRED TO BE | | | SIGNED BY THE TRUSS ENGINEER. A SIGNATURE STAMP IS NOT | | | ACCEPTABLE. FAC 61G-15-23.002 AND FS471. | | | | | | 3) THE UPLIFT FOR THE 2 PLY GIRDER (A05)TRUSS IS -2366 | | | PSF WHICH EXCEEDS THE CAPACITY OF THE HETAL 20 | | | SPECIFIED ON THE PLANS. SUBMIT REVISED ROOF FRAMING | | | PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|