| Notes |
| Date |
Text |
| 2007-04-19 08:31:03 | DENIED BY BUILDING | | | | | | 1) THE WALL SECTION ON SHEET 1 SHOWS A 3'-9" OVERHANG | | | AND THE ELEVATIONS SPECIFY 2'-0". PLEASE CORRECT. | | | | | | 2) ON SHEET 2 UNDER PREFABRICATED TRUSS NOTES, NUMBER 1 | | | REFERS TO FBC 2309. THIS SECTION IS NO LONGER USED IN | | | THE 2004 FBC. PLEASE REVISE. | | | | | | 3) ON SHEET THE ROOF SHEATHING IS REQUIRED TO BE | | | FASTENED WITH RING SHANK NAILS. SEE LATEST REVISIONS TO | | | 2004 FBC RESIDENTIAL CODE SECTION R803.2.3.1. | | | | | | 4) ON SHEET 2 THERE IS A TYPO ON SHEET 2 ON THE | | | SHEATHING FASTENING NOTES. "CDK" PLYWOOD IS SPECIFIED | | | AND IT SHOULD BE CDX. | | | | | | 5) SPECIFY THE ATTACHMENT FOR THE CONCRETE ROOF TILE. | | | CIRCLE THE FASTENER TYPE OR ADHESIVE THAT WILL BE USED | | | ON THE NOA. MAKE SURE THAT THE ATTACHMENT RESISTANCE | | | FOR THE ATTACHMENT IS ADEQUATE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|