Plan Review Notes
Plan Review Notes For Permit 07040094
Permit Number 07040094
Review Stop P
Sequence Number 3
Notes
Date Text
2008-04-28 15:52:42DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
  
 1. OK
  
 2. PER TABLE 403.1 A DRINKING FOUNTAIN AND A SERVICE
 SINK ARE REQUIRED. PLEASE SHOW THE LOCATION OF EACH ON
 THE FLOOR PLAN.
 ****DRINKING FOUNTAIN NOTED, BUT NO SERVICE SINK
 INDICATED.
 ******NO RESPONSE, COMMENT NOT ADDRESSED. SERVICE SINK
 NOT SHOWN.
  
 3. SHT A-3 INDICATES NEW PARAPET WALLS HAVE BEEN ADDED.
 SUBMIT A ROOF PLAN DETAIL SHOWING THE LOCATION OF ALL
 PRIMARY & SECONDARY ROOF DRAINS. SUBMIT CALCULATIONS
 FOR PRIMARY & SECONDARY ROOF DRAINS. SHOW THE SQUARE
 FOOTAGE OF EACH AREA BEING DRAIN BY EACH ROOF DRAIN AS
 WELL AS 1/2 AREA OF ALL VERTICAL WALLS, INCLUDING
 PARAPETS ADDED TO THE ROOF AREA OF EACH DRAIN SHOWING
 THE TOTAL AREA. SHOW THE ELEVATION OF THE ROOF & THE
 ELEVATION OF THE PARAPET WALLS. SHOW THE NORTH AND THE
 SOUTH BUILDING ELEVATIONS. SECTIONS 106.1.2, 1106 &
 1107 AS WELL AS TABLE 1106.3.
 ****ROOF PLAN INDICATED ON SHT 5.1. THE LOCATION OF THE
 SECONDARY ROOF DRAINS ARE NOT INDICATED. PLEASE SHOW
 THE LOCATION OF ALL SECONDARY ROOF DRAINS. CALCULATIONS
 INDICATE 6 RWL'S, BUT ROOF PLAN ONLY SHOWS 4. IF THERE
 ARE ONLY 4 RD'S THEN 4" RD'S AND PIPING WILL BE
 REQUIRED PER TABLE 1106.3. PLEASE CLARIFY. INDICATE THE
 SLOPE OF THE ROOF TO THE ROOF DRAINS. THE EXISTING
 CONCRETE PASS THROUGH ROOF APPEARS TO BE ABOVE THE TWO
 STORY SECTION OF THE BUILDING. PLEASE INDICATE IF ANY
 OF THIS ROOF DRAINS ON TO THE ROOF BELOW. ALSO INDICATE
 THE HEIGHT & WIDTH DIMENSIONS OF THE VERTICAL WALL
 ADJACENT TO THE LOWER ROOF ATTACHED TO THE PASS THROUGH
 ROOF. 1/2 THE AREA OF THIS WALL SHALL BE ADDED TO THE
 CALCULATIONS ALONG WITH THE PARAPET WALLS.
 ******NO COMMENT RESPONSE. THE SQUARE FOOTAGE OF EACH
 AREA IS NOT INDICATED. THE PARAPETS ARE INDICATED AS
 350.66 IN LENGHT WITH AN AVERAGE HEIGHT OF 2'0". 1/2 OF
 THAT AREA WOULD BE 350.66SF NOT 293.80SF. NO RESPONSE
 TO THE QUESTION CONCERNING THE EXISTING CONCRETE PASS
 THROUGH ROOF, NOR IS THERE ANY RESPONSE TO THE HEIGHT
 OF THE WALLL TO THE WEST SIDE OF THE NEW ROOF.--
 SHT 5.1 DETAIL FOR THE PARAPET WALL, PLEASE INDICATE
 THE ELEVATION TO THE TOP OF THE PARAPET, AS WELL AS THE
 ELEVATION OF THE ROOF AT THE PARAPET.--SUBMIT A
 SECTION FROM THE EAST SIDE OF THE NEW ROOF THRU THE
 PASS THRU ROOF SHOWING ALL ELVATIONS FOR THE ROOFS AND
 PARAPETS.--SUBMIT A DETAIL FOR THE EMERGENC
 OVERFLOW SCUPPERS SHOWING COMPLIANCE WITH SECTION
 1503.4.3.
  
 4. SUBMIT A DETAIL FOR THE REQUIRED DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH ALL
 SUBSECTIONS AS WELL SECTION 11-4.1.3(10)(A) PROVISIONS
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.
 ****DETAIL NOTED, BUT THE PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING HAS NOT BEEN ADDRESSED.
 ******DETAIL NOTED, BUT THE PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING HAS NOT BEEN
 ADDRESSED.
  
 5. OK
 6. OK
 7. OK - (DELETED)
 8. OK
  
 **********NEW COMMENT**********
  
 1B. OK
 2B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ******NO RESPONSE, NOT ADDRESSED.
  