Plan Review Notes
Plan Review Notes For Permit 07040094
Permit Number 07040094
Review Stop M
Sequence Number 3
Notes
Date Text
2008-05-01 08:32:45PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) THE SIGNATURE OF THE PREPARER ON THE ENERGY
 CALCULATIONS CAN NOT BE READ TO DETERMINE WHO'S SIGNED.
 AS NOTED IN LAST TWO REVIEWS 5-1-07 NOTE #3 AND 8-20-07
 NOTE #1. ENERGY CALCULATIONS "PREPARED BY" NEED TO BE
 SIGNED AND SEALED BY AN ARCHITECT OR ENGINEER, SEE 2004
 FBC 13-103.1.1.1 EXCEPTION.
  
 *** 2004 FBC 13-103.1.1.1 ENERGY CALCULATIONS
 COMMERCIAL APPLICATIONS. COMPLETION OF PROCEDURES
 DEMONSTRATING COMPLIANCE WITH THIS CODE FOR COMMERCIAL
 BUILDINGS SHALL BE SIGNED AND SEALED BY AN ARCHITECT OR
 ENGINEER LICENSED TO PRACTICE IN THE STATE OF FLORIDA,
 WITH THE EXCEPTION OF BUILDINGS EXCLUDED BY SECTION
 481.229, FLORIDA STATUTES , OR SECTION 471.003, FLORIDA
 STATUTES. CALCULATIONS FOR BUILDINGS FALLING WITHIN THE
 EXCEPTION OF SECTION 471.003, FLORIDA STATUTES , MAY BE
 PERFORMED BY AIR CONDITIONING OR MECHANICAL CONTRACTORS
 LICENSED IN ACCORDANCE WITH CHAPTER 489, FLORIDA
 STATUTES , OR BY STATE OF FLORIDA CERTIFIED COMMERCIAL
 BUILDING ENERGY RATERS.
 DESIGN PROFESSIONALS RESPONSIBLE UNDER FLORIDA LAW FOR
 THE DESIGN OF LIGHTING, ELECTRICAL, MECHANICAL, AND
 PLUMBING SYSTEMS AND THE BUILDING SHELL, SHALL CERTIFY
 COMPLIANCE OF THOSE BUILDING SYSTEMS WITH THE CODE BY
 SIGNING AND PROVIDING THEIR PROFESSIONAL REGISTRATION
 NUMBER ON THE ENERGY CODE FORM PROVIDED AS PART OF THE
 PLANS AND SPECIFICATIONS TO THE BUILDING DEPARTMENT.
 EXCEPTION: TYPED NAMES AND REGISTRATION NUMBERS MAY BE
 PROVIDED IN LIEU OF A SIGNATURE WHERE ALL RELEVANT
 INFORMATION HAS BEEN INCLUDED ON SIGNED AND SEALED
 PLANS.
  
 2) AS NOTED IN LAST TWO REVIEWS 5-1-07 NOTE #4 AND
 8-20-07 NOTE #2. ENERGY CALCULATIONS NEED A "MECHANICAL
 DESIGNER" WHO IS A ENGINEER, OR AN ARCHITECT, AIR
 CONDITIONING CONTRACTOR, OR MECHANICAL CONTRACTOR IF
 APPLICABLE, SEE 2004 FBC 13-103.1.1.1 AND F.S. 471.003
 (H). (NOT NELSON MARIN).
  
 3) AS NOTED IN LAST TWO REVIEWS 5-1-07 NOTE #5 AND
 4-20-07 NOTE #3. SEE MECHANICAL PLANS, TITLE BLOCK,
 (NELSON MARIN) IF NOT A LICENSE ENGINEER MAY NOT DO
 COMMERCIAL MECHANICAL PLANS, SEE F.S. 471.003. IF A
 LICENSE ENGINEER THEN HE NEEDS TO PUT HIS INFORMATION
 IN THE TITLE BLOCK, SEE FAC 61G15-23.002. LICENSE
 #CAC055529 BELONGS TO JERONIMO MARIN (NOT NELSON MARIN)
 PLEASE HAVE JERONIMO MARIN SIGN MECHANICAL PLANS.
  
 4) AS NOTED IN LAST TWO REVIEWS 5-1-07 NOTE #6 AND
 8-20-07 NOTE #4. THE COMMERCIAL MECHANICAL PLANS NEED
 TO BE DONE BY AN ENGINEER, OR A/C CONTRACTOR,
 MECHANICAL CONTRACTOR IF APPLICABLE, SEE F.S. 471.003.
 (NOT NELSON MARIN) PLEASE HAVE JERONIMO MARIN SIGN
 MECHANICAL PLANS.
  
 5) AS NOTED IN LAST TWO REVIEWS 5-1-07 NOTE #2 AND
 8-20-07 NOTE #5. PLEASE PROVIDE OUTDOOR AIR
 CALCULATIONS, AND OUTDOOR AIR, SEE 2004 FBC/M 403.1.
 (NEED TO SHOW THE CALCULATIONS ON THE MECHANICAL PLAN
 NOT JUST SHOW A FRESH AIR VENT).
  
 6) AS NOTED IN LAST REVIEW 8-20-07 NOTE #8.PLEASE
 SUBMIT COOLING LOAD CALCULATIONS, SEE 2004 FBC
 13-407.1.ABC.1.
  
 7)ENERGY CALCULATIONS NEED TO BE SIGNED BY
 OWNER/AGENT ALSO, PER 2004 FBC 13-103.3.
  
 8) INPUT REPORT PRINT-OUT IS MISSING FROM THE ENERGY
 CALCULATIONS (SHOWING THE WALL INSULATION) PLEASE
 CORRECT.
  
 9) ONLY ONE SET OF PLANS HAVE A MECHANICAL PLAN PAGE
 M-1 IN THEM BOTH SETS NEED TO HAVE A MECHANICAL PLAN
 WITH THEM, SEE 2004 FBC 106.3.5.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].