| 2008-05-04 11:22:58 | ** DENIED 3RD REVIEW ** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH NEW COMMENT(S) WHICH |
| | ARE BASED ON NEW DOCUMENTS NOW SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE 13-400.3.A AS THE VERSION OF THE |
| | SUBMITTED ENERGY CALCULATIONS MAY NOT BE USED. |
| | PLEASE KNOW VERSION 2.5 IS THE ADOPTED VERSION WHICH |
| | INCORPORATES ENERGY GAUGE SUMMIT 3.0-3.14. THIS VERSION |
| | IS STILL 2.5 AS ADOPTED. THIS HAS BEEN CONFIRMED WITH |
| | THE DEPARTMENT OF COMMUNITY AFFAIRS/FLORIDA BUILDING |
| | COMMISSION. |
| | ** PLEASE ALSO SEE THAT THE CALCULATIONS SUBMITTED ARE |
| | NOT COMPLETE. PLEASE SEE THE INPUT DATA REPORT WAS NOT |
| | SUBMITTED WHICH IS ESSENTIAL TO THE REVIEW FOR CODE |
| | COMPLIANCE. PLEASE SEE SHEET #2 ON THE SUMMARY SHEETS |
| | WHICH SPECIFICALLY STATES THE INPUT DATA REPORT MUST |
| | ACCOMPANY THE CALCULATIONS. |
| | ** PLEASE BE SURE ALL COMPONENTS OF THE BUILDING IS |
| | SHOWN ON THE IDR. PLEASE KNOW AS THIS BUILDING IS AN |
| | EXISTING BUILDING THE ONLY WAY TO USE METHOD A IS ALL |
| | COMPONENTS MUST MEET CURRENT CODES FOR INSULATIONS, |
| | WINDOWS ETC. ALL MUST BE PLACED INTO THE CALCULATIONS. |
| | PLEASE SEE 13-400.3.B, 13-101.1.3 AS THIS BUILDING DOES |
| | FALL UNDER THE DEFINITION OF A RENOVATION. PLEASE SEE |
| | THE CODE, AS A RENOVATION METHOD B OR C IS STATED. |
| | ** THIS IS IMPORTANT, METHOD *A* MAY ONLY BE USED IF |
| | ALL COMPONENTS ARE KNOWN AND MEET CURRENT CODE FOR |
| | TRADE OFF ALLOWANCES FOR *WHOLE BUILDING* ETC. |
| | THIS COMMENT IS FOR ALL TRADES WHETHER OR NOT COMMENT |
| | IS MADE BY ANY OTHER REVIEWER(S). |
| | PLEASE BE SURE TO SEE 13-415.2 FOR LIGHTING |
| | PERFORMANCE. PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND |
| | .1.3. |
| | THIS OFFICE CAN NOT EMPHASIZE ENOUGH TO PLEASE BE SURE |
| | ALL LIGHTING AND OTHER COMPONENTS ON PLANS COORDINATE |
| | WITH THE SUBMITTED ENERGY CALCULATIONS AND THE INPUT |
| | DATA REPORT. |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | PLEASE BE SURE THE OWNER/AGENT HAS SIGNED THE |
| | COMPLIANCE CERTIFICATION SHEETS. |
| | |
| | 2) NOTE: PLEASE SEE FPL STANDARDS OF METERING. PLEASE |
| | VERIFY WITH A FPL SERVICE PLANNER THAT ALL METERING |
| | DEVICES ARE GROUPED. AS THE RISER DOES NOT SHOW ANY |
| | METERING FOR INDIVIDUAL MAINS THIS CAN NOT BE VERIFIED |
| | AT THIS TIME. |
| | |
| | 3) NOTE: PLEASE SEE THE RISER HAS NOW INCLUDED |
| | CONDUCTORS FROM GUTTER TO THE MAIN HOWEVER PLEASE SEE |
| | THAT AN * EQUIPMENT GROUNDING CONDUCTOR* IS NOW BEING |
| | SHOWN WHICH IS NOT PERMITTED PER 250.6, 250.24. |
| | AS THE GROUNDED CONDUCTOR IS REQUIRED TO BE BONDED AT |
| | THE FIRST MEANS OF DISCONNECT IF AN EQUIPMENT GROUNDING |
| | CONDUCTOR WAS INSTALLED THIS WOULD PARALLEL THE NEUTRAL |
| | WHICH CREATES *OBJECTIONABLE CURRENTS*. |
| | PLEASE VERIFY ACTUAL FIRST MEANS OF DISCONNECT AND |
| | ADJUST. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |