| Date |
Text |
| 2007-09-19 17:36:55 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | |
| | 1. OK |
| | |
| | 2. PER TABLE 403.1 A DRINKING FOUNTAIN AND A SERVICE |
| | SINK ARE REQUIRED. PLEASE SHOW THE LOCATION OF EACH ON |
| | THE FLOOR PLAN. |
| | ****DRINKING FOUNTAIN NOTED, BUT NO SERVICE SINK |
| | INDICATED. |
| | |
| | 3. SHT A-3 INDICATES NEW PARAPET WALLS HAVE BEEN ADDED. |
| | SUBMIT A ROOF PLAN DETAIL SHOWING THE LOCATION OF ALL |
| | PRIMARY & SECONDARY ROOF DRAINS. SUBMIT CALCULATIONS |
| | FOR PRIMARY & SECONDARY ROOF DRAINS. SHOW THE SQUARE |
| | FOOTAGE OF EACH AREA BEING DRAIN BY EACH ROOF DRAIN AS |
| | WELL AS 1/2 AREA OF ALL VERTICAL WALLS, INCLUDING |
| | PARAPETS ADDED TO THE ROOF AREA OF EACH DRAIN SHOWING |
| | THE TOTAL AREA. SHOW THE ELEVATION OF THE ROOF & THE |
| | ELEVATION OF THE PARAPET WALLS. SHOW THE NORTH AND THE |
| | SOUTH BUILDING ELEVATIONS. SECTIONS 106.1.2, 1106 & |
| | 1107 AS WELL AS TABLE 1106.3. |
| | ****ROOF PLAN INDICATED ON SHT 5.1. THE LOCATION OF THE |
| | SECONDARY ROOF DRAINS ARE NOT INDICATED. PLEASE SHOW |
| | THE LOCATION OF ALL SECONDARY ROOF DRAINS. CALCULATIONS |
| | INDICATE 6 RWL'S, BUT ROOF PLAN ONLY SHOWS 4. IF THERE |
| | ARE ONLY 4 RD'S THEN 4" RD'S AND PIPING WILL BE |
| | REQUIRED PER TABLE 1106.3. PLEASE CLARIFY. INDICATE THE |
| | SLOPE OF THE ROOF TO THE ROOF DRAINS. THE EXISTING |
| | CONCRETE PASS THROUGH ROOF APPEARS TO BE ABOVE THE TWO |
| | STORY SECTION OF THE BUILDING. PLEASE INDICATE IF ANY |
| | OF THIS ROOF DRAINS ON TO THE ROOF BELOW. ALSO INDICATE |
| | THE HEIGHT & WIDTH DIMENSIONS OF THE VERTICAL WALL |
| | ADJACENT TO THE LOWER ROOF ATTACHED TO THE PASS THROUGH |
| | ROOF. 1/2 THE AREA OF THIS WALL SHALL BE ADDED TO THE |
| | CALCULATIONS ALONG WITH THE PARAPET WALLS. |
| | |
| | 4. SUBMIT A DETAIL FOR THE REQUIRED DRINKING FOUNTAIN |
| | SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH ALL |
| | SUBSECTIONS AS WELL SECTION 11-4.1.3(10)(A) PROVISIONS |
| | FOR THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| | ****DETAIL NOTED, BUT THE PROVISIONS FOR THOSE WHO HAVE |
| | DIFFICULTY BENDING OR STOOPING HAS NOT BEEN ADDRESSED. |
| | |
| | 5. SHT A-3 SHOW COMPLIANCE WITH THE FOLLOW: |
| | ___FOR THE W/C: |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | ****DETAIL SHOWS THE FLUSH CONTROLS ON THE WRONG SIDE |
| | OF THE TANK. |
| | ___FOR THE LAV: |
| | A. OK |
| | |
| | 6. OK |
| | 7. OK - (DELETED) |
| | 8. OK |
| | |
| | **********NEW COMMENT********** |
| | |
| | 1B. SHT 6.1 THE SANITARY PLUMBING ISOMETRIC RISER |
| | DIAGRAM DOES NOT MEET CODE REQUIREMENTS FOR SECTION |
| | 901.2.1. A VENT IS REQUIRED FOR THE DRINKING FOUNTAIN. |
| | ALSO HORIZONTAL DRY VENTS ARE NOT APPROVED PER SECTIONS |
| | 905.3 & 905.4. THE VENTS BETWEEN THE LAVS ARE NOT |
| | REQUIRED AND ARE HORIZONTAL DRY VENTS. DELETE FROM |
| | FLOOR PLAN AND RISER DIAGRAM. VENT AT EACH LAV WILL BE |
| | SUFFICIENT. |
| | |
| | 2B. FLORIDA ENERGY CALCULATIONS INDICATE NO WATER |
| | HEATER, BUT THE FLOOR PLAN AND THE RISER DIAGRAM SHOW A |
| | WATER HEATER. PLEASE CORRELATE THE INFORMATION ON THE |
| | ENERGY CALCULATIONS WITH THE FLOOR PLAN. SECTION |
| | 13-103. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |