Plan Review Notes
Plan Review Notes For Permit 07040094
Permit Number 07040094
Review Stop M
Sequence Number 2
Notes
Date Text
2007-08-20 15:51:05RETURNED TO INCOMING WAITING TO GET ON COMM. BOARD.
2007-08-20 08:57:07PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 5-1-07NOTE #3. ENERGY
 CALCULATIONS "PREPARED BY" NEED TO BE SIGNED AND SEALED
 BY AN ARCHITECT OR ENGINEER, SEE 2004 FBC 13-103.1.1.1.
 (NOT NELSON MARIN).
  
 2) AS NOTED IN LAST REVIEW 5-1-07 NOTE #4. ENERGY
 CALCULATIONS NEED A "MECHANICAL DESIGNER" WHO IS A
 ENGINEER, OR AN ARCHITECT, AIR CONDITIONING CONTRACTOR,
 OR MECHANICAL CONTRACTOR IF APPLICABLE, SEE 2004 FBC
 13-103.1.1.1 AND F.S. 471.003 (H). (NOT NELSON MARIN).
  
 *** 2004 FBC 13-103.1.1.1 COMMERCIAL APPLICATIONS.
 COMPLETION OF PROCEDURES DEMONSTRATING COMPLIANCE WITH
 THIS CODE FOR COMMERCIAL BUILDINGS SHALL BE SIGNED AND
 SEALED BY AN ARCHITECT OR ENGINEER LICENSED TO PRACTICE
 IN THE STATE OF FLORIDA, WITH THE EXCEPTION OF
 BUILDINGS EXCLUDED BY SECTION 481.229, FLORIDA STATUTES
 , OR SECTION 471.003, FLORIDA STATUTES. CALCULATIONS
 FOR BUILDINGS FALLING WITHIN THE EXCEPTION OF SECTION
 471.003, FLORIDA STATUTES , MAY BE PERFORMED BY AIR
 CONDITIONING OR MECHANICAL CONTRACTORS LICENSED IN
 ACCORDANCE WITH CHAPTER 489, FLORIDA STATUTES , OR BY
 STATE OF FLORIDA CERTIFIED COMMERCIAL BUILDING ENERGY
 RATERS.
 DESIGN PROFESSIONALS RESPONSIBLE UNDER FLORIDA LAW FOR
 THE DESIGN OF LIGHTING, ELECTRICAL, MECHANICAL, AND
 PLUMBING SYSTEMS AND THE BUILDING SHELL, SHALL CERTIFY
 COMPLIANCE OF THOSE BUILDING SYSTEMS WITH THE CODE BY
 SIGNING AND PROVIDING THEIR PROFESSIONAL REGISTRATION
 NUMBER ON THE ENERGY CODE FORM PROVIDED AS PART OF THE
 PLANS AND SPECIFICATIONS TO THE BUILDING DEPARTMENT.
 EXCEPTION: TYPED NAMES AND REGISTRATION NUMBERS MAY BE
 PROVIDED IN LIEU OF A SIGNATURE WHERE ALL RELEVANT
 INFORMATION HAS BEEN INCLUDED ON SIGNED AND SEALED
 PLANS.
  
 3) AS NOTED IN LAST REVIEW 5-1-07 NOTE #5. SEE
 MECHANICAL PLANS, TITLE BLOCK,(NELSON MARIN) IF NOT A
 LICENSE ENGINEER MAY NOT DO COMMERCIAL MECHANICAL
 PLANS, SEE F.S. 471.003. IF A LICENSE ENGINEER THEN HE
 NEEDS TO PUT HIS INFORMATION IN THE TITLE BLOCK, SEE
 FAC 61G15-23.002. LICENSE #CAC055529 BELONGS TO
 JERONIMO MARIN (NOT NELSON MARIN).
  
 4) AS NOTED IN LAST REVIEW 5-1-07 NOTE #6. THE
 COMMERCIAL MECHANICAL PLANS NEED TO BE DONE BY AN
 ENGINEER, OR A/C CONTRACTOR, MECHANICAL CONTRACTOR IF
 APPLICABLE, SEE F.S. 471.003. (NOT NELSON MARIN).
  
 5) AS NOTED IN LAST REVIEW 5-1-07 NOTE #2. PLEASE
 PROVIDE OUTDOOR AIR CALCULATIONS, AND OUTDOOR AIR, SEE
 2004 FBC/M 403.1. (NEED TO SHOW THE CALCULATIONS ON THE
 MECHANICAL PLAN NOT JUST SHOW A FRESH AIR VENT).
  
 6)SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING
 FOUR TIMES THE FEE.
  
 7) PLEASE BE ADVISED A COPY OF THE MECHANICAL PLANS AND
 ENERGY CALCULATIONS ARE BEING RETAINED AND MAY BE SENT
 TO THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATIONS.
  
 8) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-407.1.ABC.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].