| 2007-08-20 15:51:05 | RETURNED TO INCOMING WAITING TO GET ON COMM. BOARD. |
| 2007-08-20 08:57:07 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER |
| | 1 CITY OF WEST PALM BEACH AMENDMENTS. |
| | |
| | *** DENIED *** |
| | 1) AS NOTED IN LAST REVIEW 5-1-07NOTE #3. ENERGY |
| | CALCULATIONS "PREPARED BY" NEED TO BE SIGNED AND SEALED |
| | BY AN ARCHITECT OR ENGINEER, SEE 2004 FBC 13-103.1.1.1. |
| | (NOT NELSON MARIN). |
| | |
| | 2) AS NOTED IN LAST REVIEW 5-1-07 NOTE #4. ENERGY |
| | CALCULATIONS NEED A "MECHANICAL DESIGNER" WHO IS A |
| | ENGINEER, OR AN ARCHITECT, AIR CONDITIONING CONTRACTOR, |
| | OR MECHANICAL CONTRACTOR IF APPLICABLE, SEE 2004 FBC |
| | 13-103.1.1.1 AND F.S. 471.003 (H). (NOT NELSON MARIN). |
| | |
| | *** 2004 FBC 13-103.1.1.1 COMMERCIAL APPLICATIONS. |
| | COMPLETION OF PROCEDURES DEMONSTRATING COMPLIANCE WITH |
| | THIS CODE FOR COMMERCIAL BUILDINGS SHALL BE SIGNED AND |
| | SEALED BY AN ARCHITECT OR ENGINEER LICENSED TO PRACTICE |
| | IN THE STATE OF FLORIDA, WITH THE EXCEPTION OF |
| | BUILDINGS EXCLUDED BY SECTION 481.229, FLORIDA STATUTES |
| | , OR SECTION 471.003, FLORIDA STATUTES. CALCULATIONS |
| | FOR BUILDINGS FALLING WITHIN THE EXCEPTION OF SECTION |
| | 471.003, FLORIDA STATUTES , MAY BE PERFORMED BY AIR |
| | CONDITIONING OR MECHANICAL CONTRACTORS LICENSED IN |
| | ACCORDANCE WITH CHAPTER 489, FLORIDA STATUTES , OR BY |
| | STATE OF FLORIDA CERTIFIED COMMERCIAL BUILDING ENERGY |
| | RATERS. |
| | DESIGN PROFESSIONALS RESPONSIBLE UNDER FLORIDA LAW FOR |
| | THE DESIGN OF LIGHTING, ELECTRICAL, MECHANICAL, AND |
| | PLUMBING SYSTEMS AND THE BUILDING SHELL, SHALL CERTIFY |
| | COMPLIANCE OF THOSE BUILDING SYSTEMS WITH THE CODE BY |
| | SIGNING AND PROVIDING THEIR PROFESSIONAL REGISTRATION |
| | NUMBER ON THE ENERGY CODE FORM PROVIDED AS PART OF THE |
| | PLANS AND SPECIFICATIONS TO THE BUILDING DEPARTMENT. |
| | EXCEPTION: TYPED NAMES AND REGISTRATION NUMBERS MAY BE |
| | PROVIDED IN LIEU OF A SIGNATURE WHERE ALL RELEVANT |
| | INFORMATION HAS BEEN INCLUDED ON SIGNED AND SEALED |
| | PLANS. |
| | |
| | 3) AS NOTED IN LAST REVIEW 5-1-07 NOTE #5. SEE |
| | MECHANICAL PLANS, TITLE BLOCK,(NELSON MARIN) IF NOT A |
| | LICENSE ENGINEER MAY NOT DO COMMERCIAL MECHANICAL |
| | PLANS, SEE F.S. 471.003. IF A LICENSE ENGINEER THEN HE |
| | NEEDS TO PUT HIS INFORMATION IN THE TITLE BLOCK, SEE |
| | FAC 61G15-23.002. LICENSE #CAC055529 BELONGS TO |
| | JERONIMO MARIN (NOT NELSON MARIN). |
| | |
| | 4) AS NOTED IN LAST REVIEW 5-1-07 NOTE #6. THE |
| | COMMERCIAL MECHANICAL PLANS NEED TO BE DONE BY AN |
| | ENGINEER, OR A/C CONTRACTOR, MECHANICAL CONTRACTOR IF |
| | APPLICABLE, SEE F.S. 471.003. (NOT NELSON MARIN). |
| | |
| | 5) AS NOTED IN LAST REVIEW 5-1-07 NOTE #2. PLEASE |
| | PROVIDE OUTDOOR AIR CALCULATIONS, AND OUTDOOR AIR, SEE |
| | 2004 FBC/M 403.1. (NEED TO SHOW THE CALCULATIONS ON THE |
| | MECHANICAL PLAN NOT JUST SHOW A FRESH AIR VENT). |
| | |
| | 6)SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING |
| | FOUR TIMES THE FEE. |
| | |
| | 7) PLEASE BE ADVISED A COPY OF THE MECHANICAL PLANS AND |
| | ENERGY CALCULATIONS ARE BEING RETAINED AND MAY BE SENT |
| | TO THE DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| | REGULATIONS. |
| | |
| | 8) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004 |
| | FBC 13-407.1.ABC.1. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL: [email protected]. |