Plan Review Notes
Plan Review Notes For Permit 07040094
Permit Number 07040094
Review Stop B
Sequence Number 2
Notes
Date Text
2007-09-18 12:12:53CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON,CBO PERMIT NO 07040094
 BUILDING PLAN EXAMINERII PROJECT GRATITUDE
 GUILD, INC.
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS 1700 NORTH
 DIXIE HIGHWAY CONTRACTOR FRED BLAU &
 ASSOCIATES
  DATE SEPTEMBER18, 2007
  
  
 STRUCTURALPLANREVIEW
  
 1. NOTE CORRECTION SUBMITTAL
 WHEN RE-SUBMITTING CORRECTED PLANS FOR PERMITTING,
 PLEASE REMOVE AND REPLACE ANY SHEETS AS NECESSARY.
 INCLUDE A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER WITH A DESCRIPTION OF THE
 REVISION MADE. IDENTIFY THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND AND INCLUDE THE OLD
 SHEETS IN THE RE-SUBMITTAL PACKAGE FOR THE PLAN
 REVIEWER?S REFERENCE.
 THIS SHALL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2. F.S.713.13NOTICE OF COMMENCEMENT
 FILE NOTICE WITH THE CLERK OF COURT RECORDING DIVISION.
 IF THE WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED
 WITHIN 90 DAYS OF FILING THE NOTICE WILL BECOME NULL
 AND VOID. SUBMIT THE NOTICE AT THE TIME OF PERMIT
 ISSUANCE AND POST A COPY AT THE JOB SITE BEFORE THE
 FIRST INSPECTION.
  
 3. NOTESSHEET 2.1
  
 (A) CODES
 FLORIDA BUILDING CODE2004 WITH 2005 AND 2006
 REVISIONS
 FLORIDA BUILDING CODE EXISTING BUILDINGWITH 2005 AND
 2006 REVISIONS
 WEST PALM BEACH AMENDMENTS
  
 (B) PROJECT INFORMATION?PLEASE COMPLETE ON PLAN
 INFORMATION?
 CONSTRUCTION TYPE
 LEVEL OF ALTERATION III
 OCCUPANCY M / ?IDENTIFY THE STORAGE SPACE
 USING FBCCHPT. 311.1
 OCCUPANT LOAD
 OCCUPANT LOAD
 NUMBER OF FLOORS 2
 FIRST FLOOR S.F.
 SECOND FLOOR S.F.
 TOTAL EXISTING S.F.
  
  
  
  
 FBC 501.2 PREMISES IDENTIFICATION.
 APPROVED NUMBERS OR ADDRESSES SHALL BE PROVIDED FOR NEW
 BUILDINGS IN SUCH A POSITION AS TO BE CLEARLY VISIBLE
 AND LEGIBLE FROM THE STREET OR ROADWAY FRONTING THE
 PROPERTY. LETTERS OR NUMBERS SHALL BE A MINIMUM 3
 INCHES (76 MM) IN HEIGHT AND STROKE OF MINIMUM 0.5 INCH
 (12.7 MM) OF A CONTRASTING COLOR TO THE BACKGROUND
 ITSELF.
  
 FBC 602.2 TYPES I AND II.
 TYPE I AND II CONSTRUCTION ARE THOSE TYPES OF
 CONSTRUCTION IN WHICH THE BUILDING ELEMENTS LISTED IN
 TABLE 601 ARE OF NONCOMBUSTIBLE MATERIALS.
  
  
 COMMENT3D) FBC 11-4.1.6 IIACCESSIBLE BUILDINGS -
 ALTERATIONS
 PLANS DO NOT INDICATE OR IDENTIFY THE ACCESSIBLE
 ENTRANCE INTO THE BUILDING. PLANS INDICATE A 4?
 DIFFERENCE IN ELEVATION AT ENTRANCES FROM PARKING AREA
 TO UNIT SPACES.
 FBC 11-4.2??.SPACE ALLOWANCE AND REACH RANGES FBC
 11-4.3.1?.ALL WALKS/HALLS/CORRIDORS SHALL BE
 ACCESSIBLE
 FBC11-4.3.8?CHANGES IN LEVELS ALONG ACCESSIBLE
 ROUTE
 FBC11-4.1.3 (10)DRINKING FOUNTAIN MUST COMPLY WITH
 ACCESSIBILITY CODE
  
 COMMENT3E)FBC1210.1AND 1210.2 FLOORS / WALLS
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE
  
 COMMENTS 3 )
 B)USE AND OCCUPANCYCOMPLETE INFORMATION
 C) TYPE OF CONSTRUCTION
 E)SPRINKLER SYSTEM REQUIREMENT
  
 DEFINE STORAGE AREA TYPE S-1 OR S-2
 311.1 STORAGE GROUP S.
 STORAGE GROUP S OCCUPANCY INCLUDES, AMONG OTHERS, THE
 USE OF A BUILDING OR STRUCTURE, OR A PORTION THEREOF,
 FOR STORAGE THAT IS NOT CLASSIFIED AS A HAZARDOUS
 OCCUPANCY.
 311.2 MODERATE-HAZARD STORAGE, GROUP S-1.
 311.3 LOW-HAZARD STORAGE, GROUP S-2.
  
 COMMENT 4)FBC EXISTING812.4.2
 HAZARD CATEGORIES IN REGARD TO HEIGHT AND AREA SHALL BE
 IN ACCORDANCE WITH TABLE 812.4.2 .
 SEE TABLE FOR CLASSIFICATIONS
  
 COMMENT 5) WALL INSULATION VALUES ON ENERGY
 CALCULATIONS DOT NOT MATCH PLAN
  ROOFING SYSTEM TAMKO, HIGHLIGHT SYSTEM USED
 AND MATCH ENERGY CALCULATIONS FOR SPECIFIED MATERIALS
 IN SYSTEM
  
 FBC 1609.1.4IMPACT PROTECTION FOR GLAZED OPENINGS
 THIS WILL REQUIRE A SHUTTER PERMIT AND PRODUCT
 APPROVALS SUBMITTED
  
  
 F.S.713.13NOTICE OF COMMENCEMENT
 FILE NOTICE WITH THE CLERK OF COURT RECORDING DIVISION.
 IF THE WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED
 WITHIN 90 DAYS OF FILING THE NOTICE WILL BECOME NULL
 AND VOID. SUBMIT THE NOTICE AT THE TIME OF PERMIT
 ISSUANCE AND POST A COPY AT THE JOB SITE BEFORE THE
 FIRST INSPECTION.
  
  
  
  
 IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT MAY BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY.
 THE PERMITTED SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 PALM BEACH COUNTY ASSESSMENT
 PALM BEACH COUNTY IMPACT FEE ASSESSMENT HAS MOVED TO:
 2300 N JOG ROAD, SUITE 2 WPB 33411
  
 COMMENT 5)WINDOWS / DOORS PRODUCT APPROVALS
 WPB ADMINISTRATIVE CODE 106.3 REGULATED BY DCA RULE
 9B-72FLORIDA PRODUCT APPROVAL
 SUBMIT TWO COPIES OF EACH APPROVAL WITH FLORIDA PRODUCT
 APPROVAL COVER SHEET THE ARCHITECT?S / ENGINEER?S
 SIGNATURE AS APPLICABLE, STATING ?TO THE BEST OF THEIR
 KNOWLEDGE THE PRODUCT APPROVAL COMPLIES WITH THE PLANS
 AND SPECIFICATIONS.SEE:WEB SITE
 WWW.FLORIDABUILDING.COM
 NOTE: SEE DIVISION FACTOR TO BE USED IN DESIGN PRESSURE
 BY LEGACYFPA
  
 PRODUCT APPROVALS
 OUT SWING STEEL DOOR FLORIDA PRODUCT APPROVAL
 MANUFACTURER IS SUBMITTED AS JELD-WEN
 MIAMI-DADE PRODUCT APPROVAL NOTICES DOOR- CRAFT THE
 ENGINEER OF RECORD DID NOT STAMP HIS ACCEPTANCE ON THE
 MIAMI-DADE PRODUCT APPROVAL
 STORM PANEL PRODUCT APPROVAL ONLY ONE COPY SUBMITTED
 ALSO IDENTIFY WHICH SHUTTER IS BEING USED
 PLEASE REVIEW EACH PRODUCT APPROVAL, ACKNOWLEDGE EACH
 PRODUCT APPROVAL AS BEING ACCEPTED FOR THIS PROJECT AND
 IDENTIFY WHICH PRODUCT IS BEING USED
  
 DETAIL 3-3.1 IDENTIFIES THE FOOTING TO BE PLACED IN THE
 EXISTING SLAB, HOW WILL THE EXISTING FOOTING BE
 ATTACHED TO ITSELF AFTER IT IS ISOLATED BY THE NEW
 FOOTING?
  
 FURNISH TRUSS ENGINEERED DRAWINGS FOR REVIEW