Plan Review Notes
Plan Review Notes For Permit 07040094
Permit Number 07040094
Review Stop P
Sequence Number 1
Notes
Date Text
2007-06-08 16:12:32DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. PER TABLES 1004.1.2 & 403.1 SEPARATE FACILITIES ARE
 REQUIRED FOR THE MEN & WOMEN AND AS STATED IN SECTION
 403.2 UNLESS AN EXCEPTION TO THIS SECTION IS INDICATED
 ON THE PLANS AND APPROVED.
  
 2. PER TABLE 403.1 A DRINKING FOUNTAIN AND A SERVICE
 SINK ARE REQUIRED. PLEASE SHOW THE LOCATION OF EACH ON
 THE FLOOR PLAN.
  
 3. SHT A-3 INDICATES NEW PARAPET WALLS HAVE BEEN ADDED.
 SUBMIT A ROOF PLAN DETAIL SHOWING THE LOCATION OF ALL
 PRIMARY & SECONDARY ROOF DRAINS. SUBMIT CALCULATIONS
 FOR PRIMARY & SECONDARY ROOF DRAINS. SHOW THE SQUARE
 FOOTAGE OF EACH AREA BEING DRAIN BY EACH ROOF DRAIN AS
 WELL AS 1/2 AREA OF ALL VERTICAL WALLS, INCLUDING
 PARAPETS ADDED TO THE ROOF AREA OF EACH DRAIN SHOWING
 THE TOTAL AREA. SHOW THE ELEVATION OF THE ROOF & THE
 ELEVATION OF THE PARAPET WALLS. SHOW THE NORTH AND THE
 SOUTH BUILDING ELEVATIONS. SECTIONS 106.1.2, 1106 &
 1107 AS WELL AS TABLE 1106.3.
  
 4. SUBMIT A DETAIL FOR THE REQUIRED DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH ALL
 SUBSECTIONS AS WELL SECTION 11-4.1.3(10)(A) PROVISIONS
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 5. SHT A-3 SHOW COMPLIANCE WITH THE FOLLOW:
 ___FOR THE W/C:
 A. 11-4.16.5 FLUSH CONTROLS
 ___FOR THE LAV:
 A. 11-4.19.3 CLEAR FLOOR SPACE
  
 6. SUBMIT A WATER RISER DIAGRAM SHOWING ALL PIPE SIZES,
 VAVES ETC. SECTION 106.3.5.1.3(3)(10)(13).
  
 7. PER SECTION 11-4.35.4 A BENCH IS REQUIRED IN THE
 CHANGING ROOM.
  
 8. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO
 THE BUILDING. SECTION 608.13.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved