| Date |
Text |
| 2007-06-08 16:12:32 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. PER TABLES 1004.1.2 & 403.1 SEPARATE FACILITIES ARE |
| | REQUIRED FOR THE MEN & WOMEN AND AS STATED IN SECTION |
| | 403.2 UNLESS AN EXCEPTION TO THIS SECTION IS INDICATED |
| | ON THE PLANS AND APPROVED. |
| | |
| | 2. PER TABLE 403.1 A DRINKING FOUNTAIN AND A SERVICE |
| | SINK ARE REQUIRED. PLEASE SHOW THE LOCATION OF EACH ON |
| | THE FLOOR PLAN. |
| | |
| | 3. SHT A-3 INDICATES NEW PARAPET WALLS HAVE BEEN ADDED. |
| | SUBMIT A ROOF PLAN DETAIL SHOWING THE LOCATION OF ALL |
| | PRIMARY & SECONDARY ROOF DRAINS. SUBMIT CALCULATIONS |
| | FOR PRIMARY & SECONDARY ROOF DRAINS. SHOW THE SQUARE |
| | FOOTAGE OF EACH AREA BEING DRAIN BY EACH ROOF DRAIN AS |
| | WELL AS 1/2 AREA OF ALL VERTICAL WALLS, INCLUDING |
| | PARAPETS ADDED TO THE ROOF AREA OF EACH DRAIN SHOWING |
| | THE TOTAL AREA. SHOW THE ELEVATION OF THE ROOF & THE |
| | ELEVATION OF THE PARAPET WALLS. SHOW THE NORTH AND THE |
| | SOUTH BUILDING ELEVATIONS. SECTIONS 106.1.2, 1106 & |
| | 1107 AS WELL AS TABLE 1106.3. |
| | |
| | 4. SUBMIT A DETAIL FOR THE REQUIRED DRINKING FOUNTAIN |
| | SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH ALL |
| | SUBSECTIONS AS WELL SECTION 11-4.1.3(10)(A) PROVISIONS |
| | FOR THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| | |
| | 5. SHT A-3 SHOW COMPLIANCE WITH THE FOLLOW: |
| | ___FOR THE W/C: |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | ___FOR THE LAV: |
| | A. 11-4.19.3 CLEAR FLOOR SPACE |
| | |
| | 6. SUBMIT A WATER RISER DIAGRAM SHOWING ALL PIPE SIZES, |
| | VAVES ETC. SECTION 106.3.5.1.3(3)(10)(13). |
| | |
| | 7. PER SECTION 11-4.35.4 A BENCH IS REQUIRED IN THE |
| | CHANGING ROOM. |
| | |
| | 8. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO |
| | THE BUILDING. SECTION 608.13.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |