| 2007-04-16 07:38:35 | ** UNSAT ** |
| | |
| | ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO |
| | CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE |
| | CITY OF WEST PALM BEACH. |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLANS AT THIS TIME DO NOT INDICATE ANY CODES. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE COMPLETE THE ENERGY CALCULATIONS |
| | SUBMITTED. 13-415.1.AB.1.1, 13-415.2 |
| | PLEASE SEE THE SQ FT ON THE ENERGY CALCULATIONS DOES |
| | NOT CORRELATE WITH PLANS. |
| | PLEASE BE SURE TO SUBMIT THE *INPUT DATA REPORT* ALONG |
| | WITH FRONT SHEET(S) FOR PROJECT SUMMARY. (NOTE: THE |
| | CALCULATIONS ARE NOT VALID WITHOUT THE INPUT DATA |
| | REPORT) |
| | PLEASE BE SURE THE ENERGY CALCULATIONS ARE SIGNED, |
| | DATED AND SEALED BY THE RESPONSIBLE DESIGNER OF |
| | RECORD.13-103.1.1.1 |
| | PLEASE BE SURE THAT ALL LIGHTING FIXTURES, WATTAGES ETC |
| | COORDINATE WITH THE ELECTRICAL PLANS. |
| | PLEASE THE BASED ON THE LIGHTING POWER DENSITIES NOTED |
| | ON PLANS, THESE MENTION *X* WATTAGE PROVIDED, YET BASED |
| | ON THE FIXTURE LEGEND AND THE FIXTURE WATTAGES, THE LPD |
| | SEEMS TO BE HIGHER THAN THE AMOUNT SHOULD BE BASED ON |
| | THE FIXTURES AND WATTAGES LISTED. |
| | PLEASE SUBMIT A DETAIL ON LIGHTING CONTROL PANEL AS |
| | NOTED ON PLANS. THE REQUIRED LOCATIONS OF OVER RIDES |
| | FOR POINTS OF INGRESS AND EGRESS COULD NOT BE LOCATED |
| | AT THESE DOORS. ONLY ONE TIMER TYPE WAS FOUND ON PLANS. |
| | 13-415.1.ABC.1.1 |
| | PLEASE INDICATE THE MAXIMUM AMOUNT OF TIME ON THE OC |
| | TYPE DEVICES AS LISTED ON THE SYMBOL. |
| | PLEASE SEE THE STORAGE AREA WHICH CONTAINS WALL MOUNTED |
| | TYPE OCCUPANCY TYPE DEVICES ARE OK AS LONG AS COVERAGE |
| | FOR THE AREA IS MET. IF THIS IS A STORAGE AREA, HOW |
| | WILL A WALL MOUNTED DEVICE PROVIDE COVERAGE FOR THE |
| | OCCUPANTS? ARE THESE COMBINATION TYPE DEVICES? |
| | PLEASE KNOW THAT IN THE EVENT OF THE BUILDING BEING |
| | OCCUPIED AFTER HOURS AND THE TIMER TYPE DEVICE TURNS |
| | OFF, WHAT LIGHTING WILL AN OCCUPANT HAVE TO MAKE THEIR |
| | WAY SAFETY TO TURN LIGHTING BACK ON? WILL THERE BE A |
| | *NIGHT LIGHT* OR WILL AN OCCUPANCY TYPE DEVICE PROVIDE |
| | THAT COVERAGE? ONLY ONE *NL* INDICATE IN THE FRONT PART |
| | OF THE BUILDING IN RETAIL AREA. |
| | PLEASE CONSIDER. |
| | PLEASE SEE ALL OF THE NEW 2004 FBC W/2006 REVISIONS AS |
| | THERE WERE CHANGES FORM THE PREVIOUS 05, 2004 FBC. |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| | |
| | 3) NOTE: PLEASE SEE THE PLANS SEEM TO INDICATE THE MAIN |
| | SERVICE AND DISCONNECT LOCATED ON A DIFFERENT BUILDING. |
| | WHERE IS THE GUTTER AND DISCONNECTS LOCATED? PLEASE SEE |
| | 225.31-225.39 |
| | |
| | 4) NOTE: PLEASE SEE 250.32 FOR GROUNDING AT DETACHED |
| | BUILDINGS. AS THE LOCATION OF THE SERVICE IS NOT CLEAR |
| | AND THE MAIN SERVICE IS BEING SHOWN AT A DETACHED |
| | BUILDING, PLEASE SUBMIT THE DETAIL ON RISER. |
| | |
| | 5) NOTE: PLEASE COMPLETE PANEL SCHEDULE FOR LIGHTING |
| | AND RECEPTACLES. |
| | PLEASE SEE THE FOLLOWING TEXT WHICH IS FROM THE 2005 |
| | NEC 408.4. |
| | **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO |
| | REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT |
| | SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND |
| | CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE |
| | CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE |
| | MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE, |
| | SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN |
| | THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS. |
| | IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH |
| | CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE |
| | IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING |
| | ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP |
| | RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES |
| | CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR |
| | ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL |
| | REQUIRED BY THIS SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5..1.2 |
| | |
| | 6) NOTE: PLEASE SEE THE NOTES INDICATE WIRING FOR EM |
| | AND EXTLTS TO BE PER 700.12F, YET THIS SHOULD BE |
| | 700.12E. THE *F* SEEMS TO BE A MISPRINT). |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |