Plan Review Notes
Plan Review Notes For Permit 07040094
Permit Number 07040094
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-16 07:38:35** UNSAT **
  
 ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO
 CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLANS AT THIS TIME DO NOT INDICATE ANY CODES.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE COMPLETE THE ENERGY CALCULATIONS
 SUBMITTED. 13-415.1.AB.1.1, 13-415.2
 PLEASE SEE THE SQ FT ON THE ENERGY CALCULATIONS DOES
 NOT CORRELATE WITH PLANS.
 PLEASE BE SURE TO SUBMIT THE *INPUT DATA REPORT* ALONG
 WITH FRONT SHEET(S) FOR PROJECT SUMMARY. (NOTE: THE
 CALCULATIONS ARE NOT VALID WITHOUT THE INPUT DATA
 REPORT)
 PLEASE BE SURE THE ENERGY CALCULATIONS ARE SIGNED,
 DATED AND SEALED BY THE RESPONSIBLE DESIGNER OF
 RECORD.13-103.1.1.1
 PLEASE BE SURE THAT ALL LIGHTING FIXTURES, WATTAGES ETC
 COORDINATE WITH THE ELECTRICAL PLANS.
 PLEASE THE BASED ON THE LIGHTING POWER DENSITIES NOTED
 ON PLANS, THESE MENTION *X* WATTAGE PROVIDED, YET BASED
 ON THE FIXTURE LEGEND AND THE FIXTURE WATTAGES, THE LPD
 SEEMS TO BE HIGHER THAN THE AMOUNT SHOULD BE BASED ON
 THE FIXTURES AND WATTAGES LISTED.
 PLEASE SUBMIT A DETAIL ON LIGHTING CONTROL PANEL AS
 NOTED ON PLANS. THE REQUIRED LOCATIONS OF OVER RIDES
 FOR POINTS OF INGRESS AND EGRESS COULD NOT BE LOCATED
 AT THESE DOORS. ONLY ONE TIMER TYPE WAS FOUND ON PLANS.
 13-415.1.ABC.1.1
 PLEASE INDICATE THE MAXIMUM AMOUNT OF TIME ON THE OC
 TYPE DEVICES AS LISTED ON THE SYMBOL.
 PLEASE SEE THE STORAGE AREA WHICH CONTAINS WALL MOUNTED
 TYPE OCCUPANCY TYPE DEVICES ARE OK AS LONG AS COVERAGE
 FOR THE AREA IS MET. IF THIS IS A STORAGE AREA, HOW
 WILL A WALL MOUNTED DEVICE PROVIDE COVERAGE FOR THE
 OCCUPANTS? ARE THESE COMBINATION TYPE DEVICES?
 PLEASE KNOW THAT IN THE EVENT OF THE BUILDING BEING
 OCCUPIED AFTER HOURS AND THE TIMER TYPE DEVICE TURNS
 OFF, WHAT LIGHTING WILL AN OCCUPANT HAVE TO MAKE THEIR
 WAY SAFETY TO TURN LIGHTING BACK ON? WILL THERE BE A
 *NIGHT LIGHT* OR WILL AN OCCUPANCY TYPE DEVICE PROVIDE
 THAT COVERAGE? ONLY ONE *NL* INDICATE IN THE FRONT PART
 OF THE BUILDING IN RETAIL AREA.
 PLEASE CONSIDER.
 PLEASE SEE ALL OF THE NEW 2004 FBC W/2006 REVISIONS AS
 THERE WERE CHANGES FORM THE PREVIOUS 05, 2004 FBC.
 13-415.1.ABC.1.1, .1.2 AND .1.3
  
 3) NOTE: PLEASE SEE THE PLANS SEEM TO INDICATE THE MAIN
 SERVICE AND DISCONNECT LOCATED ON A DIFFERENT BUILDING.
 WHERE IS THE GUTTER AND DISCONNECTS LOCATED? PLEASE SEE
 225.31-225.39
  
 4) NOTE: PLEASE SEE 250.32 FOR GROUNDING AT DETACHED
 BUILDINGS. AS THE LOCATION OF THE SERVICE IS NOT CLEAR
 AND THE MAIN SERVICE IS BEING SHOWN AT A DETACHED
 BUILDING, PLEASE SUBMIT THE DETAIL ON RISER.
  
 5) NOTE: PLEASE COMPLETE PANEL SCHEDULE FOR LIGHTING
 AND RECEPTACLES.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS FROM THE 2005
 NEC 408.4.
 **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO
 REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5..1.2
  
 6) NOTE: PLEASE SEE THE NOTES INDICATE WIRING FOR EM
 AND EXTLTS TO BE PER 700.12F, YET THIS SHOULD BE
 700.12E. THE *F* SEEMS TO BE A MISPRINT).
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-04-16 07:04:082007-04-16 07:04:08
 IN REVIEW
2007-04-15 20:07:492007-04-15 20:07:49
 REVIEW TO CONTINUE ON 4/16