Plan Review Notes
Plan Review Notes For Permit 07040094
Permit Number 07040094
Review Stop B
Sequence Number 1
Notes
Date Text
2007-06-11 16:25:16BUILDING PLAN REVIEW
 PERMIT: 07040094
 ADD: 1700 N DIXIE HWY
 CONT: FRED BLAU & ASSOC
 TEL: (561)309-7638
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2)IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3 ) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH
 THE PROJECT ISDESIGNED.
 NOTE: THE 2004 FBC W/ 2006REVISIONS ALSO SEE 2006
 EXISTING BUILDING CODE, PROVIDE WHAT LEVEL OF
 ALTERATION TO BE COMPLETED UNDER THIS PERMIT.
 SEE CHAPTER 6 FOR LEVEL II ALTERATIONS
 AND CHAPTER 8 FOR CHANGE IN OCCUPANCY.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 NOTE THIS WILL BE FOR THE COMPLETE BUILDING
 (FOOTPRINT) , CONSISTING OF A 7,061 SQ FT TWO STORY,
 1,973 SQ FT CONCRETE PASS THROUGH AND 11,245 SQ FT
 RENOVATION TO BE
 COMPLETED UNDER THIS PERMIT.SEE DEFINITION OF
 BUILDING AREA, (FOOTPRINT). PROVIDE ANY AREA INCREASES
 IF TAKEN, PROVIDE CALCULATIONS.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G)NUMBER OF FLOORS
 H) SQ. FT. FOOTPRINT
  
 3) SHEET A-2
 3A) GENERAL NOTE# 2 PLANS INDICATE CODE SECTION
 3401.8.2.3. PLEASE CORRECT AND UPDATE.
  
 3B) GENERAL NOTE# 3 DRAFT STOPPING PER 705.3.2 PLEASE
 CORRECT AND UPDATE.
  
 3C) IS THERE TO BE A NEW FLOOR SLAB POURED AS WORK
 COMPLETED UNDER THIS PERMIT.
  
 3D) PLANS DO NOT INDICATE OR IDENTIFY THE ACCESSIBLE
 ENTRANCE INTO THE BUILDING. SHEET A-3 DETAIL C DOES
 INDICATE FROM GRADE A 4" SLAB WITH NO ACCESSIBLE ROUTE
 OR ENTRANCE.2006 EXISTING BUILDING CODE, 806.1 GENERAL.
 ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE, BUILDING
 11-4.1.2 ( 1)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING
 WITH SECTION 11-4.3 SHALL BE PROVIDED WITHIN THE
 BOUNDARY OF THE SITE FROM PUBLIC TRANSPORTATION STOPS,
 ACCESSIBLE PARKING SPACES, PASSENGER LOADING ZONES IF
 PROVIDED, AND PUBLIC STREETS OR SIDEWALKS, TO AN
 ACCESSIBLE BUILDING ENTRANCE.
 (2)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL CONNECT ACCESSIBLE BUILDINGS,
 ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS, AND
 ACCESSIBLE SPACES THAT ARE ON THE SAME SITE.
  
 3E) CHANGING ROOM 11-4.35.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE ALLOWING A PERSON USING A
 WHEELCHAIR TO MAKE A 180-DEGREE TURN SHALL BE PROVIDED
 IN EVERY ACCESSIBLE DRESSING ROOM ENTERED THROUGH A
 SWINGING OR SLIDING DOOR. NO DOOR SHALL SWING INTO ANY
 PART OF THE TURNING SPACE. TURNING SPACE SHALL NOT BE
 REQUIRED IN A PRIVATE DRESSING ROOM ENTERED THROUGH A
 CURTAINED OPENING AT LEAST 32 INCHES (815 MM) WIDE IF
 CLEAR FLOOR SPACE COMPLYING WITH SECTION 11-4.2 RENDERS
 THE DRESSING ROOM USABLE BY A PERSON USING A
 WHEELCHAIR.
  
 11-4.35.3 DOORS.
 ALL DOORS TO ACCESSIBLE DRESSING ROOMS SHALL BE IN
 COMPLIANCE WITH SECTION 11-4.13 .
  
 11-4.35.4 BENCH.
 EVERY ACCESSIBLE DRESSING ROOM SHALL HAVE A 24 INCHES
 BY 48 INCHES (610 MM BY 1219 MM) BENCH FIXED TO THE
 WALL ALONG THE LONGER DIMENSION. THE BENCH SHALL BE
 MOUNTED 17 INCHES TO 19 INCHES (430 MM TO 485 MM)
 ABOVE THE FINISH FLOOR. CLEAR FLOOR SPACE SHALL BE
 PROVIDED ALONGSIDE THE BENCH TO ALLOW A PERSON USING A
 WHEELCHAIR TO MAKE A PARALLEL TRANSFER ONTO THE BENCH.
 THE STRUCTURAL STRENGTH OF THE BENCH AND ATTACHMENTS
 SHALL COMPLY WITH SECTION 11-4.26.3 . WHERE INSTALLED
 IN
 CONJUNCTION WITH SHOWERS, SWIMMING POOLS, OR OTHER WET
 LOCATIONS, WATER SHALL NOT ACCUMULATE UPON THE SURFACE
 OF THE BENCH AND THE BENCH SHALL HAVE A SLIP-RESISTANT
 SURFACE.
  
 11-4.35.5 MIRROR.
 WHERE MIRRORS ARE PROVIDED IN DRESSING ROOMS OF THE
 SAME USE, THEN IN AN ACCESSIBLE DRESSING ROOM, A
 FULL-LENGTH MIRROR, MEASURING AT LEAST 18 INCHES WIDE
 BY 54 INCHES HIGH (460 MM BY 1370 MM), SHALL BE MOUNTED
 IN A POSITION AFFORDING A VIEW TO A PERSON ON THE BENCH
 AS WELL AS TO A PERSON IN A STANDING POSITION.
  
 3E) NEW HANDICAPPED RESTROOM, WALL FINISHES:1210.1 IN
 OTHER THAN DWELLING UNITS, TOILET AND BATHING ROOM
 FLOORS SHALL HAVE A SMOOTH, HARD, NONABSORBENT SURFACE
 THAT EXTENDS UPWARD ONTO THE WALLS AT LEAST 6 INCHES
 (152 MM).
  
 1210.2 WALLS.
 WALLS WITHIN 2 FEET (610 MM) OF URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) ABOVE THE
 FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS
 NOT ADVERSELY AFFECTED BY MOISTURE.
  
 3F) THE STORAGE AREA WITHIN THENEW THRIFT STORE
 PLEASE DECLARE IF TYPE S1 OR S2?TABLE 302.3.2.
  
 4)2006 FL EXISTING BUILDING CODE- 812.1 COMPLIANCE
 WITH CHAPTER 7 . THE OCCUPANCY CLASSIFICATION OF AN
 EXISTING BUILDING MAY BE CHANGED, PROVIDED THAT THE
 BUILDING MEETS ALL OF THE REQUIREMENTS OF CHAPTER 7
 APPLIED THROUGHOUT THE BUILDING FOR THE NEW OCCUPANCY
 GROUP AND COMPLIES WITH THE REQUIREMENTS OF SECTIONS
 802 THROUGH 812 .
 2006 FL EXISTING BUILDING CODE, CHAPTER 7 LEVEL III
 ALTERATION 708.1 MINIMUM REQUIREMENTS. ALTERATIONS
 SUBJECT TO THIS CHAPTER SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA BUILDING
 CODE, BUILDING. SEE A-3 DETAILC DOESN'T INDICATE ANY
 ROOF INSULATION.
  
 5) ENERGY CALCS ARE MISSING THE DESIGN PROFESSIONAL
 SEAL & SIGNATURE.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 6)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 6 A) JELD-WEN DOOR THE WRONG MIAMI-DADE WAS SUBMITTED
 THAT TIES TO THE FL NUMBER
 6 B) STORM PANELS- ADDITIOAL INFORMATION REQUIRED:
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED FOR ALL
 NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 FL BLD CODE 2004SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 C) TAMKO ROOFING ) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 _X__ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE _2&3__ .
  
 _X__ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 7)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL
 INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR
 THAT WERE NOT PART OF THIS REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved