| 2007-07-30 10:03:06 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | COMMENT FROM PREVIOUS LIST: |
| | |
| | 1.)THE SPAN SHOULD BE LARGER THAN THE OPENING HEIGHT. |
| | SPAN IS BLADE LENGTH.THIS MAY AFFECT ANCHOR SPACING |
| | FOR SOME OPENINGS.PLEASE REVISE SPANS AND CONFIRM |
| | ANCHOR SPACING. |
| | |
| | 4TH REVIEW - THE SPANS ARE NOW SMALLER THAN THE OPENING |
| | HEIGHT.THIS MAY BE THE CASE FOR AN INSIDE (TRAPPED) |
| | MOUNT, BUT NOT FOR A WALL MOUNT.YOU HAVE WRITTEN TWO |
| | NOTES ON THE INSTALLATION SCHEDULE.ONE STATES "ANCHOR |
| | SPACING IS FINE."PLEASE SEE OPENING 7.WITH A HEIGHT |
| | OF 100", WHEN YOU ADD THE 1 1/2 TO THE TOP AND BOTTOM |
| | OF THE OPENING FOR A WALL MOUNT, THE SPAN IS 103", OR |
| | 8'7", REQUIRING USE OF THE 9' SPAN CHART RATHER THAN |
| | THE 8' SPAN CHART AS WOULD BE REQUIRED FOR THE 96" SPAN |
| | YOU HAVE SPECIFIED.THIS DOES NOT AFFECT THE TOP MOUNT |
| | BUT DOES AFFECT ANCHOR SPACING FOR THE BOTTOM. |
| | |
| | THE SECOND NOTE STATES "WHAT ELSE KNOW?"IF YOU NEED |
| | ASSISTANCE, OR DO NOT UNDERSTAND THE CORRECTIONS, |
| | PLEASE HAVE THE QUALIFIER SCHEDULE A MEETING. |
| | |
| | NEW COMMENT: |
| | |
| | 2.)TWO COMPLETE COLLATED IDENTICAL SETS REQUIRED FOR |
| | PERMITTING.ONLY ONE NEW INSTALLATION SCHEDULE WAS |
| | SUBMITTED.IF THIS WAS THE ONLY COMMENT, I WOULD HAVE |
| | PRINTED THIS FOR YOU.HOWEVER, DUE TO WORKLOAD, I AM |
| | GENERALLY NOT ABLE TO PROVIDE COPIES AT THIS TIME. |
| | |