| | *** DENIED 2ND REVIEW *** |
| | |
| | ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO |
| | CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE |
| | CITY OF WEST PALM BEACH. |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL |
| | NEED TO BE ADDRESSED. |
| | |
| | 1) NOTE:PLEASE COMPLETE ELECTRICAL PLANS WITH |
| | ELECTRICAL AS SHOWN ON REFLECTED CEILING PLANS. PLEASE |
| | SEE MISSING INFORMATION FOR EXTERIOR LIGHTING, LOAD, |
| | SIZE AND TYPE OF FIXTURES. |
| | ONLY SOME SHOWN. |
| | PLEASE SEE FBC CHAPTER 13, 13-415.2 FOR MAXIMUM |
| | LIGHTING DENSITIES. PLEASE PROVIDE THESE ON PLANS. FBC |
| | 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK |
| | SEEMS LOW. PLEASE KNOW THE VALUE FOR WORK MUST INCLUDE |
| | ALL LABOR, MATERIALS AND EQUIPMENT EVEN IF OWNER |
| | SUPPLIED. PLEASE SEE THIS INCLUDES DESIGN COST, |
| | EQUIPMENT, FIXTURES WHICH MAY BE OWNER/CORPORATE |
| | SUPPLIED AND ALL LABOR. |
| | THE VALUE WAS NOT ADJUSTED. |
| | FBC 108.3 |
| | |
| | 3) NOTE: PLEASE SEE THE AMOUNT AND LOCATION OF THE |
| | EXISTING SHOWN EMERGENCY LIGHTS DO NOT SEEM TO PROVIDE |
| | THE MINIMUM 1FT CANDLE OF LIGHTING UNDER EMERGENCY |
| | CONDITIONS. PLEASE SEE LS 101 7.8/7.9 AND ADJUST AS |
| | NEEDED. |
| | PLEASE SEE HALLWAY OUTSIDE BATHROOMS, KITCHEN AREA AND |
| | DINING AREA OUTSIDE BATHROOMS. |
| | PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G15-23.004 |
| | WHICH REQUIRES MINIMUM LIGHTING LEVELS TO BE FIGURED |
| | FOR AREAS AS NOTED. |
| | |