Plan Review Notes
Plan Review Notes For Permit 07040087
Permit Number 07040087
Review Stop B
Sequence Number 2
Notes
Date Text
2007-09-01 13:15:14BUILDING PLAN REVIEW
 PERMIT: 07040087
 ADD: 4720 N DIXIE HWY
 CONT: NUNNO BUILDERS
 TEL: (954)961-0777
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE! WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3A)THE EDITION OF THE CODE UNDER WHICHTHE PERMIT
 WAS ISSUED. WHAT LEVEL OF ALTERATION WILL THIS BE ,
 2004 EXISTING BUILDING CODE? PLANS INDICATED LEVEL I
 PLESE SEE THE REMOVAL OF RESTROOM FACILITIES AND THE
 RECONFIGURATION MADE A LEVEL II ALTERATION. THE REMOVAL
 OF THE ROOF PARAPET,&MANSARD PLUS THE REST OF THE
 DESCRIBED WORK IN THE PROJECT WILL CLASSIFY THIS AS A
 LEVEL III ALTERATION.
  
 3B) COMPLIED.
  
 3C) PLANS INDICATE THIS BUILDING TO BE A TYPE III
 BUILDING PLEASE PROVIDE IF THIS IS A
 **A OR B**. IF THE DESIGNER WISHES TO CLASSIFY THIS AS
 A MORE RESTIVE IIA OR IIIB THE BUILDING WILL BE
 REQUIRED TO MEET THESE RATINGS. THE MINIMUM CODE
 CLASSIFIES THIS AS A VB.FOR THIS REVIEW THE REVIEWER
 WILL CONTINUE THE REVIEW AS A VB BUILDING, BUT THE NEXT
 ROUND OF COMMENTS WILL FOLLOW THE DESIGNERS DESIGNATION
 OF THE BUILDING.
  
 3D-F) COMPLIED.
  
 4) COMPLIED.
  
 5)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT
 TESTING REPORTS, MISSING REPORTS ARE AS FOLLOWS: A)
 EFIS WALL SYSTEMS MISSING THE FLORIDA COVER SHEET/
 DESIGNER OF RECORD APPROVAL
 WITH SHOP DRAWING STAMP.
 B) TRUSS ANCHORS NONE SUBMITTED WILL REQUIRE THE
 FLORIDA COVER SHEET/ DESIGNER OF
 RECORD APPROVAL WITH SHOP DRAWING STAMP.
  
 C) ROOFING ASSEMBLIES- THE FLORIDA COVER SHEET/
 DESIGNER OF RECORD APPROVAL
 WITH SHOP DRAWING STAMP. SUBSYSTEMS ARE NOT
 HIGHLIGHTED. WILL REQUIRE ENHANCED
 FASTENING IN ZONES 2 & 3. PROVIDE RAS 117
 CALCULATIONS PER LIMITATION# 7.
  
 D) FIXED/ STOREFRONT WINDOWS-NONE WERE SUPPLIED.
 PROVIDETHE FLORIDA COVER SHEET/ PRODUCT TESTING
 SHEETS & DESIGNER OF RECORD APPROVALWITH SHOP
 DRAWING STAMP.
  
  
 6)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 7) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 8A) 2ND REQUEST, SHEET A-4.1 INDICATES THE FRAMING
 DETAIL FOR THE NEWLY DESIGNEDTOWER, SHEET A-4.1
 INDICATES THE NEW TOWER HAS THE CENTER OPEN AND THE
 INSIDE WALLS HAVE A MODIFIED BITUMEN ROOFING MEMBRANE,
 THERE APPEARS TO BE NO ROOF DRAIN NOR OVERFLOW SCUPPERS
 TO ALLOW THE RAIN WATER OUT OF THIS BOX LOOKING TOWER.
 HOW WILL RAIN WATER BE DRAINED?
  
 8B) SHEET A.4.0, A.4.1 & A5.0 ALL SHOW THE PARAPET
 DETAILS, BUT NONE INDICATE HOW THE
 PARAPET WILL BE ATTACHED TO THE EXISTING STRUCTURE?
 106.1.2*/ 1609 HOW WILL THE MOMENT OF OVERTURNING BE
 RESTRICTED?
  
 9) COMPLIED CANOPY AND AWNINGS TO BE UNDER A SEPARATE
 PERMIT.
  
 10)THE NEW RESTROOM LAYOUT HAS DISCREPANCIES, SEE THE
 MEN?S RESTROOM DOOR ON SHEET A1.0 VERSES E1.0. SHEET
 A1.0 THE IN SWING DOOR INTERFERES WITH THE CLEAR FLOOR
 SPACE REQUIRED FOR THE URINAL, 11-4-18-3.SHEET E1.0
 THE DOOR BLOCKS THE EGRESS ROUTE. SEE 1005.2.
  
 11) A SECOND DISCREPANCY IS D2 VERSES A.1.0 SHEET A.1.0
 INDICATES WINDOWS 4(A) & 4(B) ON THE DEMO PLAN ONE
 WINDOW STAYS AND ONE IS REPLACED. PLEASE CORRELATE.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  