| 2007-05-17 17:08:01 | DENIED |
| | REFEREINC: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL SHEETS. THE SEAL OF THE PROFESSIONAL ENGINEER IS |
| | NOT VALID. THE FLORIDA BOARD OF ENGINEERS MANDATED A |
| | CHANGE FROM THE "CERTIFICATE" TO "LICENSE" BY FEB. 05, |
| | 2004, THEN AMENDED ITS RULING TO ALLOW A GRACE PERIOD |
| | UNTILL DEC 31 2005. (SEE ATTACHED SHEET). PLEASE USE |
| | REQUIRED SEAL. |
| | |
| | 2. ALL SHEETS. PER 61G15-23.002(1)(2) THE SIGNATURE OF |
| | THE PROFESSIONAL IS REQUIRED ON EACH SHEET. IT APPEARS |
| | THAT INITIALS HAVE BEEN USED. IF THIS IS INDEED YOUR |
| | LEGAL SIGNATURE, PLEASE SUBMIT A SIGNED, SEALED, |
| | NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE OF THE |
| | ENGINEER OF RECORD FOR OUR FILES. |
| | |
| | 3. SHT P-1.0 SANITARY RISER DIAGRAM. THE FITTING |
| | CONNECTING THE FLOOR DRAIN, (MEN'S ROOM), TO THE BRANCH |
| | LINE SHALL BE INSTALLED TO GUIDE THE WASTE IN THE |
| | DIRECTION OF FLOW. SECTION 706.3. |
| | |
| | 4. SHT ADA-1.0 SHOW COMPLIANCE WITH THE FOLLOWING: |
| | ___W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.5 FLUSH CONTROLS |
| | C. 11-4.16.6 DISPENSERS |
| | ___LAVS: |
| | A. 11-4.19.3 CLEAR FLOOR SPACE |
| | B. 11-4.19.5 FAUCETS |
| | |
| | SHOW THE W/C'S 18" OFF THE WALL TO THE CENTERLINE OF |
| | THE FIXTURE. FIG. 11-29. |
| | SHOW THE LAV'S MINIMUM OF 15" OFF THE WALL TO THE |
| | CENTERLINE OF THE FIXTURE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE |
| | SET OF THEM LOOSELY ON TOP OF THE COLLATED |
| | PLANS TO BE REVIEWED. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |